2023-01-13 17:08:44 | |
| 3RD REVIEW FBC-2020 PLUMBING |
| PERMIT- 22080874 |
| 1/3/2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) 3RD REQUEST FOR A PERMIT APPLICATION FOR THE |
| OIL/SAND INTERCEPTOR TO BE SUBMITTED. THE APPLICATION |
| SHALL NOT BE SUBMITTED UNDER THIS PERMIT BUT SEPARATELY |
| AS THE YOU HAVE SUBMITTED THE BACKFLOW. AS PREVIOUSLY |
| NOTED, I CANNOT APPROVE THE PLUMBING PLANS WITHOUT |
| SUBMITTAL OF THE PERMIT APPLICATION FOR THE OIL |
| INTERCEPTOR. BASED ON THE RESUBMITTED PLUMBING |
| SPECIFYING A SEPARATE PERMIT APPLICATION FOR THE WATER |
| REUSE SYSTEM AND RECLAIM TANKS, I CANNOT APPROVE THE |
| PLANS WITHOUT SUBMITTAL OF THAT PERMIT APPLICATION. |
| THIS WILL ENSURE THAT PERMIT ISSUANCE AND INSPECTIONS |
| WILL BE DONE IN TIMELY AND ORDERLY MANNER. PLEASE SEE |
| PREVIOUS COMMENT BELOW- |
| |
| PLEASE NOTE THAT DUE TO A CHANGE IN PROCESS, THE |
| BACKFLOW AND OIL INTERCEPTOR PERMITS ARE REQUIRED TO BE |
| SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU |
| CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF |
| YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| COMPLETED PERMIT APPLICATION TO [email protected] |
| . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| TO PASS. |
| |
| 2) SHEETS P1, P4: PLEASE REVISE THE OIL/SAND ISOMETRIC |
| DRAWING TO MATCH THE NEW PIPING LAYOUT SHOWN ON P1- |
| SEC. 107.2.1 WPB. IT ALSO APPEARS THE LOCATIONS OF THE |
| RECLAIM AND OIL DRAIN PIPES AND DRAIN PIPE SIZES ON |
| SHEET 3.4 (TRENCH DRAIN CROSS SECTION) DO NOT MATCH |
| WITH REVISED P1. |
| |
| 3) P1: SCH 80 PVC SPECIFIED FOR VACUUM PIPING ON THE |
| SITE PLAN, HOWEVER THE SUBMITTED SHOP DRAWINGS SPECIFY |
| SCH 40. PLEASE CLARIFY IF THE SYSTEM WILL BE PART OF |
| THE MAIN PERMIT OR IF TO BE INSTALLED UNDER A SEPARATE |
| PERMIT- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |