Plan Review Notes
Plan Review Notes For Permit 22080874
Permit Number 22080874
Review Stop P
Sequence Number 3
Notes
Date Text
2023-01-13 17:08:44 
 3RD REVIEW FBC-2020 PLUMBING
 PERMIT- 22080874
 1/3/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 3RD REQUEST FOR A PERMIT APPLICATION FOR THE
 OIL/SAND INTERCEPTOR TO BE SUBMITTED. THE APPLICATION
 SHALL NOT BE SUBMITTED UNDER THIS PERMIT BUT SEPARATELY
 AS THE YOU HAVE SUBMITTED THE BACKFLOW. AS PREVIOUSLY
 NOTED, I CANNOT APPROVE THE PLUMBING PLANS WITHOUT
 SUBMITTAL OF THE PERMIT APPLICATION FOR THE OIL
 INTERCEPTOR. BASED ON THE RESUBMITTED PLUMBING
 SPECIFYING A SEPARATE PERMIT APPLICATION FOR THE WATER
 REUSE SYSTEM AND RECLAIM TANKS, I CANNOT APPROVE THE
 PLANS WITHOUT SUBMITTAL OF THAT PERMIT APPLICATION.
 THIS WILL ENSURE THAT PERMIT ISSUANCE AND INSPECTIONS
 WILL BE DONE IN TIMELY AND ORDERLY MANNER. PLEASE SEE
 PREVIOUS COMMENT BELOW-
  
 PLEASE NOTE THAT DUE TO A CHANGE IN PROCESS, THE
 BACKFLOW AND OIL INTERCEPTOR PERMITS ARE REQUIRED TO BE
 SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU
 CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 2) SHEETS P1, P4: PLEASE REVISE THE OIL/SAND ISOMETRIC
 DRAWING TO MATCH THE NEW PIPING LAYOUT SHOWN ON P1-
 SEC. 107.2.1 WPB. IT ALSO APPEARS THE LOCATIONS OF THE
 RECLAIM AND OIL DRAIN PIPES AND DRAIN PIPE SIZES ON
 SHEET 3.4 (TRENCH DRAIN CROSS SECTION) DO NOT MATCH
 WITH REVISED P1.
  
 3) P1: SCH 80 PVC SPECIFIED FOR VACUUM PIPING ON THE
 SITE PLAN, HOWEVER THE SUBMITTED SHOP DRAWINGS SPECIFY
 SCH 40. PLEASE CLARIFY IF THE SYSTEM WILL BE PART OF
 THE MAIN PERMIT OR IF TO BE INSTALLED UNDER A SEPARATE
 PERMIT- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  