2022-11-28 13:35:31 | ELECTRIC REVIEW FAILED |
| 1) ELECTRIC RISER DIAGRAM DETAILS (2) ELECTRIC PANELS |
| FOR WHAT IS ASSUMED TO BE THE MAIN HOUSE. THESE PANELS |
| ARE DETAILED AS BEING FED WITH 2/0 CU CONDUCTORS. 2/0 |
| CU CONDUCTORS FEEDING ONLY PART OF THE MAIN HOUSE ARE |
| NOT PERMITTED TO BE DE-RATED TO 83%. ONLY CONDUCTORS |
| SUPPLYING THE ENTIRE LOAD ASSOCIATED WITH A DWELLING IS |
| PERMITTED TO BE DE-RATED TO 83%. IN ADDITION, ALL 6 OF |
| THESE CONDUCTORS ARE DETAILED AS BEING IN THE SAME |
| CONDUIT WHICH WOULD REQUIRE FURTHER DERATING AS PER NEC |
| 310.15(B)(3). PLEASE CORRECT AS APPLICABLE FOR CODE |
| COMPLIANCE |
| 2) THE ELECTRIC RISER DIAGRAM DOES NOT DETAIL SIZE OF |
| SERVICE OR ANY MAIN DISCONNECTS. PLEASE DETAIL SERVICE |
| SIZE AND ALL MAIN OVERCURRENT PROTECTION AS REQUIRED |
| PER NEC 215.5 AND NEC 240.4 |
| 3) PLEASE DETAIL ALL MAIN DISCONNECTS AS GROUPED IN ONE |
| LOCATION AND MARKED TO INDICATE THE LOAD SERVED AS PER |
| NEC 230.72 |
| 4) PLEASE DETAIL GROUNDING ELECTRODE CONNECTIONS IN |
| PROPER LOCATIONS NOT CONNECTED TO CONDUITS. NEC215.5 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |