2022-10-19 12:24:47 | ELECTRIC REVIEW FAILED | | | | 1) PLEASE LOCATE ALL ELECTRIC EQIPMENT ON A SITE PLAN | | AS THE SERVICE ORIGINATES AT A SEPARATE STRUCURE AS | | THIS INFORMATION IS REQUIRED TO DO A COMPLETE | | ELECTRICAL REVIEW. FBC 107.2 | | 2) RISER DIAGRAMS MAIN DISCONNECTS NOT GROUPED AS | | REQUIRED PER NEC 230.72. PLEASE CORRECT AS APPLICABLE | | 3) PLEASE SEE ZONING REVIEW AS THIS STRUCTURE APPEARS | | TO BE PROHIBITED. FBC 107.2 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|