 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 210.52 (A) IN EVERY KITCHEN, FAMILY ROOM, DINING ROOM,
 LIVING ROOM, PARLOR, LIBRARY, DEN, SUNROOM, BEDROOM,
 RECREATION ROOM, OR SIMILAR ROOM OR AREA OF DWELLING
 UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE GENERAL PROVISIONS SPECIFIED IN
 210.52(A)(1) THROUGH (A)(4).
  
 BALCONIES, DECKS, AND PORCHES THAT ARE ATTACHED TO THE
 DWELLING UNIT AND ARE ACCESSIBLE FROM INSIDE THE
 DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE FROM THE BALCONY, DECK, OR PORCH. THE
 RECEPTACLE OUTLET SHALL NOT BE LOCATED MORE THAN 2.0 M
 (61???2 FT) ABOVE THE BALCONY, DECK, OR PORCH WALKING
 SURFACE.