Plan Review Notes
Plan Review Notes For Permit 22080802
Permit Number 22080802
Review Stop G
Sequence Number 1
Notes
Date Text
2022-08-19 16:45:32 
 1ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22080802
 8/19/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLUMBING PERMIT FOR THE GAS-FIRED TANKLESS WATER
 HEATER HAS BEEN CHANGED TO A GAS PERMIT. THE PROJECT IS
 NOT A LIKE-FOR-LIKE REPLACEMENT. WPB BUILDING DEPT.
 RECORDS INDICATE A 75,000 BTU GAS FIRED STORAGE TANK
 WATER HEATER WAS APPROVED UNDER PERMIT 04041190 IN
 APRIL 2004. THERE ARE NO OTHER GAS PERMITS ON RECORD
 SINCE THAT DATE. THE SUBMITTED SPECS FOR THE NAVIEN
 WATER HEATER INDICATE A RANGE OF MODELS FROM 120,000-
 199,900 BTUS. PLEASE INDICATE WHICH MODEL IS TO BE
 INSTALLED AND PROVIDE A GAS RISER IN COMPLIANCE WITH
 SECS. G2412.3 & G2412.4 FBC RES. THE RISER SHALL SHOW:
  
 A) TYPE OF GAS- NATURAL OR LP.
 B) DELIVERY PRESSURE AT THE METER.
 C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 D) TYPES AND SIZES OF PIPING.
 E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 G) LOCATIONS OF REGULATORS, SHUTOFF VALVES.
 H) OUTLET PRESSURES AT REGULATORS.
 I) LOCATIONS AND TYPES OF PIPE SLEEVES.
 K) PIPE SIZING TABLES.
  
 2) PROVIDE A BASIC FLOOR PLAN SHOWING THE LOCATION OF
 THE WATER HEATER- SEC. 107.2.1 WPB. PLEASE NOTE THAT
 COMBUSTION AIR AND VENTING PLANS ARE REQUIRED FOR
 INDOOR INSTALLATIONS- REFER TO SECS. G2407.1, G2427.8,
 & G2448.1 FBC RES. IF THE UNIT IS TO BE INSTALLED ON
 THE EXTERIOR, PLEASE PROVIDE CLEARANCE DISTANCES TO
 GRADE, OPERABLE WINDOWS AND DOORS, AND OTHER AIR
 INTAKES INTO THE BUILDING- SEC. G2447.8.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.