Date |
Text |
2022-09-06 10:11:29 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL10124-R31 HAS BEEN REVISED TO FL10124-R32. |
| PLEASE PROVIDE A COMPLETE SET OF PRODUCT APPROVALS. |
| INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| PRODUCT APPROVAL DRAWINGS. |
| 2. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL |
| SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH |
| NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS. |
| PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT |
| INDICATE ON ROOF DRAWING/SKETCH). |
| 3. FBC B 107.2.1 SUBMITTED ROOF DIAGRAM/SKETCH APPEARS |
| TO INDICATE REROOFING LOW/FLAT SLOPE AREA & LOWER TILE |
| ROOF AREA; IF NOT INDICATE BY PLACING AN X IN LOW/FLAT |
| SLOPE AREAS & LOWER TILE ROOF AREAS; IF TO RECEIVE NEW |
| ROOFING PROVIDE A COMPLETE SET OF 2020 CODE VERSION |
| PRODUCT APPROVALS/NOA'S FOR THE PROPOSED FLAT ROOF & |
| TILE ROOF SYSTEMS TO BE USED. INCLUDE COVER PAGE, |
| EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR |
| SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS |
| MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL |
| DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY |
| COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC |
| ENGINEERING. REVISE ROOF DIAGRAM/SKETCH TO INCLUDE MEAN |
| ROOF HEIGHT(S). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |