Plan Review Notes
Plan Review Notes For Permit 22080683
Permit Number 22080683
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-31 13:10:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22080683
 ADD: 3905 WASHINGTON RD. CHANGE OF OCCUPANCY
 CONT: TBD/ TO BE DETERMINED
 TEL:
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT. 31ST/ 2022
 ACTION: DENIED
 1) THE PERMIT APPLICATION AND FLOOR PLAN BOTH STATE
 LARGE FAMILY DAYCARE. THE CHANGE OF OCCUPANCY HAS TO BE
 DETERMINED. THE DESIGNER OF THE FLOOR PLAN HAS NOT
 GIVEN US AN OCCUPANT LOAD. IN THE 2020 FBC-BUILDING
 CODE TABLE 1004.5 HAS AN OCCUPANT LOAD FACTOR OF 35 SQ.
 FT./ OCCUPANT.
 BEDROOM # 1 11X12 = 132 SQ FT/ 35 = 4 OCCUPANTS.
 BEDROOM # 2 11X12 = 132 SQ FT / 35= 4 OCCUPANTS
 LIVING ROOM & DINING ROOM
 278.76 SQ FT /35 SQ FT = 8 OCCUPANTS
 TOTAL OCCUPANT LOAD 16 OCCUPANTS.
 PLEASE PROVIDE A BREAKDOWN OF CHILDREN BY AGE AND HOW
 MANY IN EACH AGE GROUP.
  
 2020 FBC-B SECTION 466.10 DAY CARE HOMES ARE NOT MORE
 THAN 12 CLIENTS WHO RECEIVE CARE, MAINTENANCE AND
 SUPERVISION BY OTHERS NOT BY RELATIVES FOR LESS THAN 24
 HOURS PER DAY. NOT A DAY CARE HOME.
  
 1A) 2020 FBC-B SECTION 308.3.3. SIX TO 16 PERSONS
 RECEIVING CUSTODIAL CARE. A FACILITY HOUSING NOT FEWER
 THAN 6 AND NOT MORE THAN 16 PERSONS RECEIVING CUSTODIAL
 CARE SHALL BE CLASSIFIED AS GROUP R-4.
 FBC-BUILDING 308.3.2. CONDITION 2. WHERE ANY PERSONS
 (INFANTS & TODDLERS) RECEIVING CUSTODIAL CARE WHO
 REQUIRE LIMITED VERBAL OR PHYSICAL ASSISTANCE WHILE
 RESPONDING TO AN EMERGENCY SITUATION TO COMPLETE
 BUILDING EVACUATION.
  
 2020 FBC-EXISTING BUILDING CODE 1004.1 FIRE PROTECTION
 REQUIREMENTS OF THIS SECTION 1012 SHALL APPLY WHERE A
 BUILDING OR PORTIONS THERE OF UNDERGO CHANGE OF
 OCCUPANCY CLASSIFICATION OR WHERE THERE IS A CHANGE OF
 OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT
 FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER
 9 OF THE FBC-BUILDING.
  
 2020 FBC-BUILDING CODE 903.2.8.3 GROUP R-4 CONDITION 2.
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN ACCORDANCE
 WITH SECTION 903.1.2 (NFPA 13R SPRINKLER SYSTEM) SHALL
 BE PERMITTED IN GROUP R4 CONDITION 2 OCCUPANCIES.
 ATTICS SHALL BE PROTECTED IN ACCORDANCE WITH SECTION
 903.2.8.3.1 OR 903.2.8.3.2.
  
 1B) PLEASE SHOW LOCATIONS OF PORTABLE FIRE
 EXTINGUISHERS IN COMPLIANCE WITH 2020 FBC-BUILDING CODE
 SECTION 906.1 WHERE REQUIRED.
  
 1C) 2020 FBC-EXISTING BUILDING CODE 1004.1 FIRE
 PROTECTION REQUIREMENTS OF THIS SECTION 1012 SHALL
 APPLY WHERE A BUILDING OR PORTIONS THERE OF UNDERGO
 CHANGE OF OCCUPANCY CLASSIFICATION OR WHERE THERE IS A
 CHANGE OF OCCUPANCY WITHIN A SPACE WHERE THERE IS A
 DIFFERENT FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT
 IN CHAPTER 9 OF THE FBC-BUILDING. (FIRE ALARM).
  
 2020 FBC-BUILDING 907.2.10. FIRE ALARM SYSTEMS AND
 SMOKE ALARMS SHALL BE INSTALLED IN GROUP R-4
 OCCUPANCIES AS REQUIRED IN SECTIONS 907.2.10.1 THROUGH
 907.2.10.3.
  
 1D) IF THERE ARE ANY KINDERGARTEN OR PRE-KINDERGARTEN
 CHILDREN THEN REQUIREMENTS FROM THE 2020 FBC-BUILDING
 CHAPTER 453 WILL BE ALSO ENFORCE.
  
 1E) FLORIDA ADMINISTRATIVE CODE 65C-22.002 CHILD CARE
 STANDARDS.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  