2022-08-17 13:32:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS NO FLOOR PLAN SHOWING THE LOCATIONS OF THE |
| PROPOSED FLOORING. |
| |
| PER NFPA 1 |
| |
| 1.7.12 PLANS AND SPECIFICATIONS. |
| |
| 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| APPLICABLE CODES AND STANDARDS. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN |
| INDICATING THE LOACTION OF THE PROPOSED FLOORING. |
| |
| |
| |
| 2) THERE ARE INDICATIONS OF FLOOR INFO BUT NO |
| SPECIFICATIONS SHEETS THAT INDICATE MEETING THE |
| REQUIREMENTS PER NFPA |
| |
| VINYL LAMINATE FLOORING CAN BE MANUFACTURED AROUND THE |
| CLOCK BUT NOT MEET THE REQUIRMENTS OF NFPA. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7* INTERIOR FLOOR FINISH TESTING AND |
| CLASSIFICATION. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN |
| THE CLASSES SPECIFIED |
| IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE |
| CRITICAL RADIANT FLUX |
| REQUIREMENTS. |
| |
| 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I |
| INTERIOR FLOOR FINISH |
| SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| 0.45 W/CM2, AS DETERMINED |
| BY THE TEST DESCRIBED IN 10.2.7.3. |
| |
| 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II |
| INTERIOR FLOOR FINISH |
| SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN |
| 0.22 W/CM2, BUT LESS |
| THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN |
| 10.2.7.3. |
| |
| PLEASE REVIEW AND PROVIDE SPEC SHEET OF THE PROPOSED |
| VINYL LAMINATE FLOORING. |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |