Plan Review Notes
Plan Review Notes For Permit 22080613
Permit Number 22080613
Review Stop R
Sequence Number 1
Notes
Date Text
2022-09-20 11:31:22PLAN REVIEW ROOFING
  
 1ST ROOFING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: A ROOFING SUB-PERMIT IS REQUIRED.
 PERMITS - 105.1 REQUIRED.
  
 1. PROVIDE PRODUCT APPROVALS FOR SECONDARY WATER
 BARRIER PER FBC R905.1.1.
 UNDERLAYMENT FOR ROOF SLOPES 2:12 AND GREATER SHALL
 CONFORM TO THE APPLICABLE STANDARDS??? AND SHALL BE
 APPLIED AND ATTACHED IN ACCORDANCE WITH SECTION
 R905.1.1.1, R905.1.1.2 OR R905.1.1.3, AS APPLICABLE.
  
 R905.3.3UNDERLAYMENT. CONCRETE TILE.
 REQUIRED UNDERLAYMENT SHALL COMPLY WITH THE
 UNDERLAYMENT MANUFACTURER???S INSTALLATION INSTRUCTIONS
 IN ACCORDANCE WITH THE FRSA/TRI FLORIDA HIGH WIND
 CONCRETE AND CLAY ROOF TILE INSTALLATION MANUAL, SIXTH
 EDITION WHERE THE VASD IS DETERMINED IN ACCORDANCE WITH
 SECTION R301.2.1.3 OR THE RECOMMENDATIONS OF RAS 118,
 119 OR 120.
  
 2. DESIGNER SHALL SELECT THE INSTALLATION METHOD OF THE
 ROOF TILE. IF ADHESIVE IS TO BE USED, PROVIDE THE
 PRODUCT APPROVAL OF THE ADHESIVE.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  