Plan Review Notes
Plan Review Notes For Permit 22080521
Permit Number 22080521
Review Stop M
Sequence Number 2
Notes
Date Text
2022-09-27 17:04:222ND REVIEW FMC
 PERMIT: 22080521
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 2ND ATTEMPT FOR THE COMMENTS BELOW. THE AREA LEADING
 FROM THE STAIRWAY TO THE EAST SIDE OF THE BUILDING IS
 AN EXIT PASSAGEWAY BY DEFINITION. FBC EXIT PASSAGEWAY.
 AN EXIT COMPONENT THAT IS SEPARATED FROM OTHER INTERIOR
 SPACES OF A BUILDING OR STRUCTURE BY FIRE-RESISTANCE-
 RATED CONSTRUCTION AND OPENING PROTECTIVES, AND
 PROVIDES FOR A PROTECTED PATH OF EGRESS TRAVEL IN A
 HORIZONTAL DIRECTION TO AN EXIT OR TO THE EXIT
 DISCHARGE.
 THERE CAN BE NOTHING IN OR PASSING THROUGH THIS EXIT
 PASSAGEWAY. THE VAV-16 MUST BE REMOVED. THERE CAN BE NO
 RETURN, OR SUPPLY GRILLES PENETRATING THE RATED
 CEILING. IF THIS EXIT PASSAGEWAY IS TO BE CONDITIONED
 IT MUST BE CONDITIONED INDEPENDENTLY FROM THE BUILDINGS
 MECHANICAL SYSTEMS. 2ND ATTEMPT FOR THE COMMENTS BELOW.
 ORIGINAL REVIEW COMMENTS:
  
 1) THE REDESIGN OF THE OPEN AREA OF THE 1ST FLOOR INTO
 TENANT SPACES HAS CREATED EXIT PASSAGEWAYS. PLEASE
 REMOVE ALL DUCTWORK AND SYSTEMS FROM THESE EXIT
 PASSAGEWAYS. FMC 601.3
 [BF] 601.3 EXITS. EQUIPMENT AND DUCTWORK FOR EXIT
 ENCLOSURE VENTILATION SHALL COMPLY WITH ONE OF THE
 FOLLOWING ITEMS:
  
 1. SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED
 EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY
 CONNECTED TO THE EXIT ENCLOSURE BY DUCTWORK ENCLOSED IN
 CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING FOR SHAFTS.
  
 2. WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN
 THE EXIT ENCLOSURE, THE INTAKE AIR SHALL BE TAKEN
 DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE
 DISCHARGED DIRECTLY TO THE OUTDOORS, OR SUCH AIR SHALL
 BE CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS
 REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING FOR
 SHAFTS.
  
 3.WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT AND
 DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF THE
 BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, WITH
 CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING CODE,
 BUILDING FOR SHAFTS.
  
  
 IN EACH CASE, OPENINGS INTO FIRE-RESISTANCE-RATED
 CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR
 MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY
 SELF-CLOSING FIRE-RESISTANCE- RATED DEVICES IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING FOR
 ENCLOSURE WALL OPENING PROTECTIVES. EXIT ENCLOSURE
 VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER
 BUILDING VENTILATION SYSTEMS.
  
 2) THE OUTDOOR AIR CALCULATIONS MUST MEET FMC 403.3.1.1
 AND TABLE 403.3.1.1. BASED ON THE OCCUPANCY AND SQUARE
 FOOTAGE IN THE OUTDOOR AIR CALCULATIONS PRESENTED ON
 SHEET M1.2 THE LOBBY IS REQUIRED TO HAVE 1031 CFM???S
 OF OUTDOOR AIR; THE MAIL ROOM IS NOT AN OCCUPANCY
 LISTED IN TABLE 403.3.1.1, PLEASE USE AN OCCUPANCY
 LISTED IN THE TABLE THAT CLOSELY RESEMBLES THE USE LIKE
 MAYBE THE STORAGE, PICK UP; THE ENTRANCE/EXIT IS ALSO
 NOT AN OCCUPANCY LISTED IN TABLE 403.3.1.1, PLEASE PICK
 AN OCCUPANCY THAT BEST MEETS THE REQUIREMENTS AND
 PROVIDE CALCULATIONS BASED ON THAT OCCUPANCY. FMC
 403.3.1.1 AND TABLE 403.3.1.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  