2022-09-27 17:04:22 | 2ND REVIEW FMC |
| PERMIT: 22080521 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 2ND ATTEMPT FOR THE COMMENTS BELOW. THE AREA LEADING |
| FROM THE STAIRWAY TO THE EAST SIDE OF THE BUILDING IS |
| AN EXIT PASSAGEWAY BY DEFINITION. FBC EXIT PASSAGEWAY. |
| AN EXIT COMPONENT THAT IS SEPARATED FROM OTHER INTERIOR |
| SPACES OF A BUILDING OR STRUCTURE BY FIRE-RESISTANCE- |
| RATED CONSTRUCTION AND OPENING PROTECTIVES, AND |
| PROVIDES FOR A PROTECTED PATH OF EGRESS TRAVEL IN A |
| HORIZONTAL DIRECTION TO AN EXIT OR TO THE EXIT |
| DISCHARGE. |
| THERE CAN BE NOTHING IN OR PASSING THROUGH THIS EXIT |
| PASSAGEWAY. THE VAV-16 MUST BE REMOVED. THERE CAN BE NO |
| RETURN, OR SUPPLY GRILLES PENETRATING THE RATED |
| CEILING. IF THIS EXIT PASSAGEWAY IS TO BE CONDITIONED |
| IT MUST BE CONDITIONED INDEPENDENTLY FROM THE BUILDINGS |
| MECHANICAL SYSTEMS. 2ND ATTEMPT FOR THE COMMENTS BELOW. |
| ORIGINAL REVIEW COMMENTS: |
| |
| 1) THE REDESIGN OF THE OPEN AREA OF THE 1ST FLOOR INTO |
| TENANT SPACES HAS CREATED EXIT PASSAGEWAYS. PLEASE |
| REMOVE ALL DUCTWORK AND SYSTEMS FROM THESE EXIT |
| PASSAGEWAYS. FMC 601.3 |
| [BF] 601.3 EXITS. EQUIPMENT AND DUCTWORK FOR EXIT |
| ENCLOSURE VENTILATION SHALL COMPLY WITH ONE OF THE |
| FOLLOWING ITEMS: |
| |
| 1. SUCH EQUIPMENT AND DUCTWORK SHALL BE LOCATED |
| EXTERIOR TO THE BUILDING AND SHALL BE DIRECTLY |
| CONNECTED TO THE EXIT ENCLOSURE BY DUCTWORK ENCLOSED IN |
| CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING CODE, |
| BUILDING FOR SHAFTS. |
| |
| 2. WHERE SUCH EQUIPMENT AND DUCTWORK IS LOCATED WITHIN |
| THE EXIT ENCLOSURE, THE INTAKE AIR SHALL BE TAKEN |
| DIRECTLY FROM THE OUTDOORS AND THE EXHAUST AIR SHALL BE |
| DISCHARGED DIRECTLY TO THE OUTDOORS, OR SUCH AIR SHALL |
| BE CONVEYED THROUGH DUCTS ENCLOSED IN CONSTRUCTION AS |
| REQUIRED BY THE FLORIDA BUILDING CODE, BUILDING FOR |
| SHAFTS. |
| |
| 3.WHERE LOCATED WITHIN THE BUILDING, SUCH EQUIPMENT AND |
| DUCTWORK SHALL BE SEPARATED FROM THE REMAINDER OF THE |
| BUILDING, INCLUDING OTHER MECHANICAL EQUIPMENT, WITH |
| CONSTRUCTION AS REQUIRED BY THE FLORIDA BUILDING CODE, |
| BUILDING FOR SHAFTS. |
| |
| |
| IN EACH CASE, OPENINGS INTO FIRE-RESISTANCE-RATED |
| CONSTRUCTION SHALL BE LIMITED TO THOSE NEEDED FOR |
| MAINTENANCE AND OPERATION AND SHALL BE PROTECTED BY |
| SELF-CLOSING FIRE-RESISTANCE- RATED DEVICES IN |
| ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING FOR |
| ENCLOSURE WALL OPENING PROTECTIVES. EXIT ENCLOSURE |
| VENTILATION SYSTEMS SHALL BE INDEPENDENT OF OTHER |
| BUILDING VENTILATION SYSTEMS. |
| |
| 2) THE OUTDOOR AIR CALCULATIONS MUST MEET FMC 403.3.1.1 |
| AND TABLE 403.3.1.1. BASED ON THE OCCUPANCY AND SQUARE |
| FOOTAGE IN THE OUTDOOR AIR CALCULATIONS PRESENTED ON |
| SHEET M1.2 THE LOBBY IS REQUIRED TO HAVE 1031 CFM???S |
| OF OUTDOOR AIR; THE MAIL ROOM IS NOT AN OCCUPANCY |
| LISTED IN TABLE 403.3.1.1, PLEASE USE AN OCCUPANCY |
| LISTED IN THE TABLE THAT CLOSELY RESEMBLES THE USE LIKE |
| MAYBE THE STORAGE, PICK UP; THE ENTRANCE/EXIT IS ALSO |
| NOT AN OCCUPANCY LISTED IN TABLE 403.3.1.1, PLEASE PICK |
| AN OCCUPANCY THAT BEST MEETS THE REQUIREMENTS AND |
| PROVIDE CALCULATIONS BASED ON THAT OCCUPANCY. FMC |
| 403.3.1.1 AND TABLE 403.3.1.1. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |