2022-09-27 17:18:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22080521
 ADD: 1501 BELVEDERE RD 1ST FLOOR COMMON AREAS
 CONT: VREDEX CONSRUCTION
 TEL: 561-440-1600
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. SEPT. 27TH/2022
 ACTION: DENIED
  
 1) COMPLIED.
  
 2)COMPLIED. SHEET A0.4 THE FLOOR PLAN THE LIFE SAFETY
 PLAN SHOWS THE EAST INTERIOR EXIT STAIRWAYS CONTINUING
 TO THE EXIT BY A 2-HOUR FIRE RATED EXIT PASSEAGE WAY
 WITH 90- MINUTE OPENING PROTECTIVES.
  
 2A-B) COMPLIED.
  
 2C) 2ND REQUEST. PLEASE REVIEW SHEET M1.2 FOR ALL
 DUCTWORK AND RELATED MECHANICAL EQUIPMENT THAT IS
 LOCATED IN THE CEILINGS OF BOTH THE EAST EXIT
 PASSAGEWAY. PLEASE REVIEW SECTION 1024.6 PENETRATIONS
 INTO OR THROUGH EXIT PASSAGEWAYS, PROHIBITED, PLUMBING,
 MECHANICAL EQUIPMENT, AND ELECTRICAL PIPING AND
 DEVICES. 2020 FBC-BUILDING. THE RESPONSE THE ENGINEER
 HAS ADDED A 2- HOUR SHAFT WALL CEILING DETAIL TO
 CONCEAL THE DUCTWORK. SHAFTWALL ARE BUILT FLOOR TO
 CEILING, THEY ARE TO BE BUILT WITH STRUCTURAL METAL
 STUDS, U415 IS FOR NONBEARING WALL RATING. WHILE NOT
 TESTED BY UL, THE SYSTEM HAS BEEN TESTED FOR FIRE AND
 IS COVERED FOR USE THROUGHOUT THE UNITED STATES. THE
 FIRE TEST NUMBER IS WHI 495-PSH-0154/0167 AND REPORT
 NUMBER IS AER-09038 AVAILABLE AT WWW.P-E-I.COM.ALSO SEE
 CAVITY SHAFTWALL SYSTEMS, TECHNICAL DATA FOR MAXIMUM
 HORIZONTAL SPANS FOR I-STUD ASSEMBLIES 2 HR. FIRE
 RESTRICTIVE RATING, HORIZONTAL SHAFTWALL DUCT AND
 CEILING ASSEMBLIES 09 21 16.23/NGC BUYLINE1100. PROVIDE
 A SHAFTWALL ASSEMBLY THAT HAS A 2 HOUR FIRE RATING
 WHERE IT HAS BEEN TESTED HORIZONTALLY.
  
 2D-E) COMPLIED.
  
 3)COMPLIED.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  