Date |
Text |
2022-08-23 11:49:31 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22080521 |
| ADD: 1501 BELVEDERE RD 1ST FLOOR COMMON AREAS |
| CONT: VREDEX CONSRUCTION |
| TEL: 561-440-1600 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. AUGUST 23/2022 |
| ACTION: DENIED |
| |
| 1) SHEET A0.0 THE COVERSHEET: |
| 1A) PROJECT DATA LIST THIS BUILDING AS 4 STORIES. PALM |
| BEACH COUNTY MY GEO NAV SHOWS A 5 STORY BUILDING AND |
| VIEWING THE BUILDING FROM THE WEST A BASEMENT/ ENCLOSED |
| PARKING LEVEL. ADDITIONAL INFORMATION REQUIRED, |
| 107.2.1. DISCREPANCY IN PLANS. |
| |
| 1B) THE EAST STAIR ENCLOSURE SHOWS THE STAIRS GOING |
| DOWN INTO THE BASEMENT/ GARAGE LEVEL. MISSING ON THE |
| WEST STAIR ENCLOSURE. ADDITIONAL INFORMATION REQUIRED, |
| 107.2.1. DISCREPANCY IN PLANS. |
| |
| 2) SHEET A0.4 THE FLOOR PLAN DETAIL ON THE COVERSHEET |
| AND LIFE SAFETY PLAN SHOWS BOTH THE EAST AND WEST |
| INTERIOR EXIT STAIRWAYS CONTINUING TO THE EXIT BY A 2 |
| HOUR FIRE RATED EXIT PASSAGE WAY, INCLUSIVE OF THE |
| LOBBY AREA. |
| 2A) PLEASE REVIEW IN THE 2020 FBC-BUILDING CODE SECTION |
| 1024.5OPENINGS. REVIEW THE LAST LINE, ELEVATORS SHALL |
| NOT OPEN INTO EXIT PASSAGEWAYS. |
| |
| 2B) THE LOBBY WALLS AND CORRIDOR ARE CURRENTLY SHOWN AS |
| 2 HOUR EXIT PASSAGE WAY RATED WALLS, BUT THE OPENINGS |
| LEADING TO THE RESTROOM CORRIDOR 109 DO NOT HAVE |
| OPENING PROTECTIVE DOORS RATED 1 1/2 HRS. AS REQUIRED |
| BY TABLE 716.5 IF THIS AREA REMAINED A 2HOUR EXIT |
| PASSAGEWAY. |
| |
| 2C) PLEASE REVIEW SHEET M1.2 FOR ALL DUCTWORK AND |
| RELATED MECHANICAL EQUIPMENT THAT IS LOCATED IN THE |
| CEILINGS OF BOTH THE EAST AND WEST EXIT PASSAGEWAYS. |
| PLEASE REVIEW SECTION 1024.6 PENETRATIONS INTO OR |
| THROUGH EXIT PASSAGEWAYS, PROHIBITED, PLUMBING, |
| MECHANICAL EQUIPMENT, AND ELECTRICAL PIPING AND |
| DEVICES. 2020 FBC-BUILDING. |
| |
| 2D) THERE ARE NO WALL IDENTIFICATION TAGS IN THE EXIT |
| PASSAGEWAY INDICATING THESE WALLS ARE 2-HOUR FIRE |
| RESISTANCE RATING. 2-HOUR VERTICAL EXITS, INTERIOR EXIT |
| STAIRWAYS, REQUIRE THE EXIT PASSAGEWAY TO MAINTAIN THE |
| SAME LEVEL OF FIRE RATING (FIRE BARRIERS) SECTION |
| 1023.2 & 1024.3. |
| |
| 2E) THE EAST INTERIOR EXIT DOOR SWINGS INTO THE EXIT |
| RATHER THAN SWINGING OUT AS THE DIRECTION OF EGRESS |
| TRAVEL PER 1010.1.2.1. THE DOOR WOULD NEED TO BE FITTED |
| WITH 180 DEGREE HINGES TO SWING FLAT AGAINST THE WALL. |
| 3) SHEET A3.2 WALL DETAILS DO NOT INCLUDE A UL WALL |
| ASSEMBLY FOR A 2 HOUR FIRE RESISTANCE RATED WALL.2020 |
| FBC-BUILDING CODE SECTION 707.3.4 EXIT PASSAGEWAYS. |
| |
| 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |