Plan Review Notes For Permit 22080520 |
Permit Number |
22080520 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-08-17 10:59:22 | FIRE PROVISO COMMENTS: | | | | ALL LIFE SAFETY SYSTEMS (FIRE SPRINKLER AND/OR FIRE | | ALARM) SHALL REMAIN FULLY OPERATIONAL DURING ALL PHASES | | OF DEMOLITION AND CONSTRUCTION. | | | | ANY IMPAIRMENT TO ANY LIFE SAFETY SYSTEM (FIRE | | SPRINKLER AND/OR FIRE ALARM) THAT EXCEEDS 4 CONTINUOUS | | HOURS IN DURATION WILL REQUIRE THE IMPLEMENTATION OF A | | FIRE WATCH. | | | | ANY WORK (RELOCATION, MODIFICATIONS, ETC.) ON ANY LIFE | | SAFETY SYSTEM (FIRE SPRINKLER AND/OR FIRE ALARM) WILL | | REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS. | | | | ANY WORK ON ANY LIFE SAFETY SYSTEM (FIRE SPRINKLER | | AND/OR FIRE ALARM) SHALL BE DONE BY PROPERLY LICENSED | | AND QUALIFIED CONTRACTORS. | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | | | |
|