Plan Review Notes
Plan Review Notes For Permit 22080480
Permit Number 22080480
Review Stop M
Sequence Number 2
Notes
Date Text
2022-12-14 08:24:252ND REVIEW FMC
 PERMIT: 22080480
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ATTACHED DRAWINGS ARE NOT READABLE PLEASE SUBMIT
 EACH ORIGINAL ON A SEPARATE PAGE AS THE ONES SUBMITTED
 ARE COPIES AND ARE NOT CLEAR, CANNOT READ THE WORDS. A
 COMPLETE SET OF DRAWINGS WERE NOT SUBMITTED AS I DO NOT
 SEE THE MAKE UP AIR CALCULATIONS. SHEET 2 OF 3
 INDICATES 4 DIFFERENT COMPANIES THAT MANUFACTURE
 DUCTWORK FOR THE ROASTERS WITH AN AFTERBURNER. NORDFAB
 IS NOT ON THAT LIST. PLEASE PROVIDE THE SPECIFICATIONS
 FROM THE ONE THAT WILL BE USED IN THIS DESIGN. THE
 DUCTWORK DETAILS ON SHEETS M-3 AND SHEET 2 OF 2 DO NOT
 MATCH. THE INSTALLATIONS OF EACH ROASTER AND THE
 AFTERBURNER MUST BE SUBMITTED, SHEET M-1 IS NOT
 READABLE.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  