Plan Review Notes
Plan Review Notes For Permit 22080480
Permit Number 22080480
Review Stop M
Sequence Number 1
Notes
Date Text
2022-08-16 10:29:471ST REVIEW FMC
 PERMIT: 22080480
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THIS SUBMITTAL IS INCOMPLETE SO I CANNOT DO A
 REVIEW. THE INFORMATION SUBMITTED IS COPIES OF THE
 DOCUMENTS AND ARE NOT CLEAR. PLEASE PROVIDE THE
 INSTALLATION INSTRUCTIONS FOR EACH ROASTER AND THE
 NORDFAB DUCTWORK. FBC 107.3.5
  
 2) PLEASE PROVIDE A BUILDING PERMIT APPLICATION AND
 ARCHITECTURAL DRAWINGS FOR THE INSTALLATION OF THESE
 ROASTERS AND THE PENETRATIONS OF THE ROOF IN THIS
 WAREHOUSE. PROVIDE THE OCCUPANCY CLASSIFICATION THAT
 THIS BUILDING WILL BE RECLASSIFIED TO WITH THIS
 INSTALLATION. FBC 107.3.5
  
 3) WHAT IS THE FUEL SOURCE FOR THESE ROASTERS? IF THEY
 ARE GAS FIRED THEN A FUEL GAS PERMIT WOULD BE REQUIRED.
  
 4) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THE
 INSTALLATION OF THESE ROASTERS INCLUDING THE REQUIRED
 COMBUSTION AND MAKEUP AIR. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  