2022-08-16 10:29:47 | 1ST REVIEW FMC |
| PERMIT: 22080480 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THIS SUBMITTAL IS INCOMPLETE SO I CANNOT DO A |
| REVIEW. THE INFORMATION SUBMITTED IS COPIES OF THE |
| DOCUMENTS AND ARE NOT CLEAR. PLEASE PROVIDE THE |
| INSTALLATION INSTRUCTIONS FOR EACH ROASTER AND THE |
| NORDFAB DUCTWORK. FBC 107.3.5 |
| |
| 2) PLEASE PROVIDE A BUILDING PERMIT APPLICATION AND |
| ARCHITECTURAL DRAWINGS FOR THE INSTALLATION OF THESE |
| ROASTERS AND THE PENETRATIONS OF THE ROOF IN THIS |
| WAREHOUSE. PROVIDE THE OCCUPANCY CLASSIFICATION THAT |
| THIS BUILDING WILL BE RECLASSIFIED TO WITH THIS |
| INSTALLATION. FBC 107.3.5 |
| |
| 3) WHAT IS THE FUEL SOURCE FOR THESE ROASTERS? IF THEY |
| ARE GAS FIRED THEN A FUEL GAS PERMIT WOULD BE REQUIRED. |
| |
| 4) PROVIDE A COMPLETE MECHANICAL DESIGN FOR THE |
| INSTALLATION OF THESE ROASTERS INCLUDING THE REQUIRED |
| COMBUSTION AND MAKEUP AIR. FBC 107.3.5 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |