Date |
Text |
2023-01-31 10:19:26 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22080480 |
| ADD: 2603 PINEWOOD AVE. |
| CONT: HIGH TECH DUCTWORKS |
| TEL: 772-559-6913 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. JAN. 31/ 2023 |
| ACTION: DENIED |
| |
| 1) THE LAST KNOWN USE FOR THIS SPACE WAS A STORAGE |
| OCCUPANCY. PLEASE PROVIDE A FLOOR PLAN FOR THE WHOLE |
| BUILDING SINCE IS A CHANGE OF USE AND CHANGE OF |
| OCCUPANCY. THE 2020 EXISTING BUILDING CODE CHAPTER 10 |
| SECTION 1001.2.2 WILL NEED TO BE MET. SINCE THIS IS OUT |
| OF THE SCOPE OF YOUR LICENSE A DESIGN PROFESSIONAL MAY |
| BE REQUIRED FOR ALL TRADES. 2020 W. P. B. |
| ADMINISTRATIVE CODE107.3.5 MINIMUM PLAN REVIEW CRITERIA |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATIVE CODE SECTION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| OR STRUCTURES. MISSING ALL PLANS FOR A CHANGE OF |
| OCCUPANCY. |
| |
| |
| 2) THE SHEET M-3 IS ILLEGIBLE CANNOT MAKE OUT THE |
| WORDING. 107.2.1.3. QUALITY OF PLANS. THE BUILDING |
| OFFICIAL MAY ESTABLISH THROUGH DEPARTMENT POLICY OTHER |
| STANDARDS FOR THE PLANS AND SPECIFICATIONS IN ORDER TO |
| PROVIDE CONFORMITY TO ITS RECORD RETENTION PROGRAM. |
| THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| RECORD MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE |
| WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| |
| 2A) THERE IS A PENETRATION TO WHAT APPEARS TO BE A |
| CONCRETE DECK. EITHER SINGLE T OR DOUBLE T, THE PLANS |
| ARE NOT CLEAR IN THIS MATTER. THE DETAIL DOES NOT STATE |
| IF THESE ARE EXISTING PENETRATIONS THROUGH THE CONCRETE |
| ROOF DECK OR NOT, PLEASE DECLARE, THIS IS ALSO OUT OF |
| THE SCOPE OF YOUR LICENSE F S 489.105(3) (D) SHEET |
| METAL CONTRACTOR. |
| IF NEW PROVIDE DETAIL HOW THE NEW ROOF PENETRATION IS |
| TO PROCEED, SIZE OF PENETRATION AND IF ANY ADDITIONAL |
| RE-ENFORCING IS REQUIRED. 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE |
| SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. |
| |
| 3) SHEET M-3DOES NOT INCORPORATES WIND DESIGN. |
| 2020 FBC-B 1603.1.4 WIND DESIGN CRITERIA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| |
| 3.2. RISK CATEGORY. |
| |
| 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1. |
| |
| 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| THE DESIGN OF THE STRUCTURE, PSF. |
| |
| 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| CONVERSION VULT TO VASD. |
| |
| 4) SHEET M-3DOES NOT INCORPORATE THE ANCHORING OF THE |
| ROOF TOP CURB, STACK (SIZE OF FLUE) OR CAP. ONE FLUE IS |
| 5 FEET ABOVE THE ROOF THE OTHER IS 5FEET 4 INCHES. 2020 |
| FBC-M- 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT, |
| APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL |
| BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES |
| DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| CODE, BUILDING.FBC-B-1609.6.4.4.1 COMPONENTS AND |
| CLADDING. WIND PRESSURE FOR EACH COMPONENT OR CLADDING |
| ELEMENT IS TO BE DESIGNED FOR WIND PRESSURES COMPONENTS |
| AND ATTACHMENTS. 2020 FBC-B 1604.4 ANALYSIS. LOAD |
| EFFECTS ON STRUCTURAL MEMBERS AND THEIR CONNECTIONS |
| SHALL BE DETERMINED BY METHODS OF STRUCTURAL ANALYSIS |
| THAT TAKE INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, |
| GEOMETRIC COMPATIBILITY AND BOTH SHORT- AND LONG-TERM |
| MATERIAL PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED |
| TO RESIST THE OVERTURNING EFFECTS CAUSED BY THE LATERAL |
| FORCES SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR |
| WIND LOADS. |
| |
| 5) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS |
| AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.6.4.4.1 |
| COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY |
| AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 |
| NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(C) PANEL WALLS:, WALL LOUVERS, D) ROOFING PRODUCTS |
| AND ASSEMBLIES |
| |
| 6) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP |
| DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC. |
| |
| 7) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT |
| REMARKS MAYBE MADE IN THE NEXT REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |