Plan Review Notes
Plan Review Notes For Permit 22080414
Permit Number 22080414
Review Stop E
Sequence Number 3
Notes
Date Text
2023-02-15 12:14:26ELECTRIC REVIEW FAILED
  
 1) IT APPEARS THE ELECTRICAL RISER PROVIDED DOES NOT
 MATCH THE ELECTRICAL RISER DIAGRAM ON FILE FROM A
 PREVIOUS ELECTRICAL UPGRADE DONE IN 2012. PLEASE
 PROVIDE A CORRECT ELECTRIC RISER TO COMPLY WITH CODES
 CITED BELOW.
 .
 NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER
 DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF
 THE FEEDERS.
  
 FBC 107.2, CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  