2022-09-16 13:17:33 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY THE THICKNESS AND REINFORCING FOR THE 2 FT | | TALL SHEER DESCENT WALL. FBC 107.2.1 | | | | 2) SPECIFY THE NUMBER OF TAPCONS THAT IS REQUIRED FOR | | EACH PIECE OF POOL EQUIPMENT. FBC 107.2.1 | | | | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|