2023-02-21 15:03:59 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 22080286 |
| ADD: 1701 S FLAGLER DR # 1901 |
| CONT: CONRAD CONSTRUCTION |
| TEL: 561-512-7637 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. FEB. 21ST/2023 |
| ACTION: DENIED |
| |
| 1) 2ND REQUEST. SUBMITTED PROFLEX MSC 90 UNDERLAYMENT, |
| SUBMITTED IS A SALES BROCHURE, NOT TEST RESULTS. |
| PROFLEX MSC MEGA SOUND CONTROL HAS NOT BEEN TESTED FOR |
| 6-INCH CONCRETE SLABS BUT PROFLEX DOES HAVE PROFLEX |
| SUPER SIM 90 THAT HAS ALL 3 REQUIRED TEST, FOR TILE AND |
| MARBLE IIC, STC AND FLAME SPREAD. |
| 1ST ROUND OF COMMENTS. SHEET A-1 UNDER THE HEADING |
| SCOPE OF WORK LIST THE DEMO OF FLOOR TILE AND INSTALL |
| NEW FLOOR TILE THROUGHOUT THE UNIT. SOUNDPROOFING |
| BARRIER AS APPROVED BY CONDO ASSOCIATION. THIS REVIEW |
| THERE WERE NO SOUNDPROOFING DOCUMENT SUBMITTED. |
| FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| STONE, MARBLE FLOORING ALL NEED TO HAVE HAD THE SOUND |
| UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/ |
| NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 1A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE |
| SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS |
| OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 1B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1. |
| EXCEPTION 2. (TILE & MARBLE) INSULATION INSTALLED |
| BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| SPREAD INDEX OF NOT MORE THAN 200. |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 2-3) COMPLIED: ISSUED WINDOW PERMIT 22090284. |
| |
| 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| |
| MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| PART-TIME/ SEMI-RETIRED. |
| |
| IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| BACK INTO THE OFFICE CALL |
| (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| THANK YOU. |
| |