Plan Review Notes For Permit 22080266 |
Permit Number |
22080266 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-10-06 17:18:59 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SPECIFY HOW THE POOL EQUIPMENT WILL BE ANCHORED TO | | RESIST WINDLOADS. SPECIFY THE FASTENER TYPE, SIZE AND | | THE NUMBER REQUIRED FOR EACH PIECE OF POOL EQUIPMENT. | | SPECIFY THE REQUIRED EMBED DEPTH FOR THE FASTENERS. FBC | | 107.2.1 | | 2) THE EXISTING POOL FENCE IS REQUIRED TO BE PERMITTED | | AND BELONG TO THE POOL OWNER. FBC FBCR 4501.17 |
|