2022-11-18 17:22:47 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 22080258 |
| 11/18/22 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE COD |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A3-00: COMPLIANCE WITH DISPERSION OF THE |
| ACCESSIBLE UNITS WAS CALLED OUT IN 1ST REVIEW COMMENT |
| #2B IN ACCORDANCE WITH SEC. 224.5 FBC ACC. THE UNIT |
| MATRIX SUMMARY DOES NOT APPEAR TO SHOW COMPLIANCE WITH |
| 8 ADA STUDIO UNITS, 2 ADA 1-BED UNITS, AND 1 ADA 2-BED |
| UNIT. PLEASE REVIEW SEC. 224.5- |
| "GUEST ROOMS REQUIRED TO PROVIDE MOBILITY FEATURES |
| COMPLYING WITH 806.2 AND GUEST ROOMS REQUIRED TO |
| PROVIDE COMMUNICATION FEATURES COMPLYING WITH 806.3 |
| SHALL BE DISPERSED AMONG THE VARIOUS CLASSES OF GUEST |
| ROOMS, AND SHALL PROVIDE CHOICES OF TYPES OF GUEST |
| ROOMS, NUMBER OF BEDS, AND OTHER AMENITIES COMPARABLE |
| TO THE CHOICES PROVIDED TO OTHER GUESTS." |
| |
| 2) SHEET A3-00: THE MATRIX ADA SUITES MOBILITY LIST |
| DESIGNATES STUDIO 740 AS A "FLORIDA ACCESSIBLE UNIT". |
| THIS APPEARS TO BE A MISLABEL AND SHOULD INDICATE FAIR |
| HOUSING COMPLIANCE BASED ON SHEET A3-19B WHICH SHOWS A |
| TYPE B BATHROOM LAYOUT FOR UNIT 740- SEE PAGE 7.34 FAIR |
| HOUSING DESIGN ACT MANUAL. PLEASE NOTE THAT ALL ADA |
| SUITES SHALL ALSO BE DESIGNED AND CONSTRUCTED IN |
| COMPLIANCE WITH THE FLORIDA ACCESSIBILITY CODE. |
| |
| 3) SHEET A3-10A, UNIT 3A HC MISSING OR INCORRECT |
| DETAILS PER FBC ACC. |
| A) DETAIL 1: SHOW THE CLEAR FLOOR DEPTH MEASUREMENT AT |
| THE WATER CLOSET- SEC. 604.3. |
| B) DETAIL 1: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| DIMENSIONS FOR A FORWARD APPROACH TO THE LAVATORY- SEC. |
| 606.2. |
| C) DETAILS 6 & 8: SHOW THE KNEE AND TOE CLEARANCES FOR |
| THE LAVATORY- SEC. 606.2 & FIGURES 306.2 & 306.3. |
| D) DETAIL 8: SHOW THE HEIGHT OF THE WATER CLOSET WILL |
| BE 17-IN. MIN. AND 19-IN. MAX. FROM THE FINISHED FLOOR |
| TO THE TOP OF THE SEAT- SEC. 604.4. |
| E) DETAIL 1 & 6: SHOW THE WATER CLOSET GRAB BAR LENGTHS |
| AND SPACINGS PER FIGURES 694.5.1 & 604.5.2. |
| F) DETAIL 1: SHOW THE 30 X 60 IN. CLEAR FLOOR SPACE |
| DIAGRAM AT THE SHOWER- SEC. 608.2.2.1. |
| G) DETAILS 1,7, 8: SHOW SHOWER GRAB BAR LENGTHS AND |
| SPACINGS FROM ADJACENT WALLS- SEC. 608.3.2. |
| H) DETAILS 7 & 8: SHOW THE ROLL-IN SHOWER THRESHOLD |
| HEIGHT- SEC. 608.7. |
| I) DETAIL 7: SHOW THE HEIGHT OF THE SHOWER SEAT FROM |
| THE SHOWER FLOOR TO THE TOP OF THE SEAT- 610.2. |
| J) PROVIDE DIMENSIONED TUB AND SHOWER SEAT DIAGRAMS AND |
| INDICATE THE TUB SEAT IS REMOVABLE AND THE SHOWER SEAT |
| IS A FOLDING TYPE- SEC. 610.3- 610.4. |
| |
| 4) SHEET A3-15A, UNIT B2B HC MISSING OR INCORRECT |
| DETAILS PER FBC ACC. |
| A) DETAIL 1: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| DIMENSIONS FOR A FORWARD APPROACH TO THE LAVATORY- SEC. |
| 606.2 |
| B) DETAILS 6: SHOW THE KNEE AND TOE CLEARANCES FOR THE |
| LAVATORY- SEC. 606.2 & FIGURES 306.2 & 306.3. |
| C) DETAIL 6: SHOW THE HEIGHT OF THE WATER CLOSET WILL |
| BE 17-IN. MIN. AND 19-IN. MAX. FROM THE FINISHED FLOOR |
| TO THE TOP OF THE SEAT- SEC. 604.4. |
| D) DETAIL 1 & 6: SHOW THE WATER CLOSET GRAB BAR LENGTHS |
| AND SPACINGS PER FIGURES 694.5.1 & 604.5.2. |
| E) DETAIL 1: SHOW THE CLEAR WIDTH AND DEPTH |
| MEASUREMENTS OF THE WALK-IN SHOWER, AND THE 36 X 48 IN. |
| CLEAR FLOOR SPACE ENTRY ON THE FACE OF THE COMPARTMENT |
| MEASURED FROM THE CONTROL WALL- SEC. 608.2.1. |
| F) DETAILS 1,7, 8: SHOW SHOWER GRAB BAR LENGTHS AND |
| SPACINGS FROM ADJACENT WALLS- SEC. 608.3.1. |
| G) DETAIL 8: SHOW THE SHOWER CONTROLS, FAUCET, AND |
| SPRAY SHALL BE LOCATED ON THE CONTROL WALL 15-INCHES |
| MAXIMUM FROM THE CENTERLINE OF THE SEAT TOWARD THE |
| SHOWER OPENING. |
| H) DETAIL 7: SHOW THE HEIGHT OF THE SHOWER SEAT FROM |
| THE SHOWER FLOOR TO THE TOP OF THE SEAT- 610.2 |
| I) DETAIL 6: PROVIDE A DIMENSIONED SHOWER SEAT DIAGRAM |
| AND INDICATE THE SHOWER SEAT IS A FOLDING TYPE- SEC. |
| 610.3- 610.4. |
| |
| 5) SHEET A3-19A, UNIT E1F.4HC MISSING OR INCORRECT |
| DETAILS PER FBC ACC: PLEASE SEE COMMENT #3 ABOVE FOR |
| SIMILAR DEFICIENCIES AND PROVIDE CORRECTIONS- SEC. |
| 107.2.1 WPB. |
| |
| 6) SHEET A3-29A, UNIT E2G.1 MISSING OR INCORRECT |
| DETAILS PER FBC ACC: PLEASE REVIEW COMMENT #2 FOR |
| SIMILAR DEFICIENCIES AND PROVIDE CORRECTIONS- SEC. |
| 107.2.1 WPB. |
| |
| 7) SHEET A3-19B, UNIT E1F.4 FAIR HOUSING COMPLIANCE. |
| A) DETAILS 1, 3 & 5: PLEASE SHOW THE LENGTHS OF THE |
| WATER CLOSET GRAB BARS- PAGE 6.5 FAIR HOUSING DESIGN |
| ACT MANUAL. |
| |
| 8) SHEETS A-3-10A, A3-15A, A3-19A, A3-19B, A3-29A: THE |
| CLEAR FLOOR SPACE DIAGRAM POSITIONED FOR A FORWARD |
| APPROACH TO THE KITCHEN SINK DOES NOT APPEAR TO INCLUDE |
| THE REQUIRED KNEE AND TOE CLEARANCES. PLEASE CLARIFY IF |
| THE CABINETS ARE DESIGNED TO ALLOW THE CLEARANCES FOR A |
| FORWARD APPROACH OR PROVIDE A PARALLEL APPROACH- SEC. |
| 606.2 FBC ACC. |
| |
| 9) SHEETS P3-15A & P-15 DETAIL 4: SHOW THE WASHING |
| MACHINE DRAIN CONNECTION TO THE WASTE STACK- SEC. 913.2 |
| FBC P. |
| |
| 10) 2ND REQUEST. SHEETS P1-01B & P4-01: PROVIDE THE |
| MAKES AND MODELS OF THE FACILITY WASHING MACHINES AND |
| SUBMIT MANUFACTURER'S SPECIFICATIONS- SECS. 406.1 & |
| 406.2 FBC P. THE MACHINES MUST DISCHARGE BY GRAVITY, |
| AND LINT INTERCEPTORS ARE REQUIRED- SEC. 1003.6 FBC P. |
| REVISE THE PIPING DRAWING TO SHOW THE LOCATION AND |
| PIPING CONNECTIONS TO THE INTERCEPTOR. |
| |
| 11) 2ND REQUEST TO PROVIDE WATER RISER DRAWINGS. |
| DRAWINGS ARE PROVIDED FOR THE INDIVIDUAL UNITS HOWEVER |
| RISERS NOT PROVIDE FOR THE LAUNDRY ROOM AND THE THE |
| PIPING TO THE 24 FACILITY WATER HEATERS SHOWN IN THE |
| GAS RISER- SEC. 107.3.5.1.3 WPB. |
| |
| 12) PLEASE PROVIDE A FLOOR PLAN DRAWING SIMILAR TO |
| SHEET P1-01B THAT SHOWS THE LOCATIONS OF THE 24- GAS |
| WATER HEATERS AND GAS AND WATER PIPING LAYOUTS- SEC. |
| 107.2.1 WPB. |
| |
| 13) PLEASE SHOW COMPLIANCE ON THE PLANS WITH SEC. |
| 607.1.1 FBC P AND PROVIDE MASTER THERMOSTATIC MIXING |
| VALVES AT THE WATER HEATER IN THE LAUNDRY ROOM AND FOR |
| THE FACILITY WATER HEATERS. |
| |
| 14) P4-01: THE PLUMBING FIXTURE SCHEDULES IS MISSING |
| MANY ITEMS INCLUDING THE KITCHEN SINKS, DISHWASHERS, |
| KITCHEN AND LAVATORY FAUCETS, SHOWER VALVES AND FAUCETS |
| AND SPRAYS, TUB AND SHOWER VALVES AND FAUCETS, AND |
| WASHING MACHINES- SEC. 107.2.1 WPB. THE SCHEDULE ALSO |
| LISTS ONLY ONE ADA COMPLIANT SHOWER AND THERE IS A |
| WALK-IN AND ROLL-IN TYPE. PLEASE PROVIDE A COMPLETE |
| FIXTURE SCHEDULE AND AS PREVIOUSLY REQUESTED SUBMIT |
| SPECS FOR THE ADA SHOWERS. THE SHOWERS AND OTHER |
| FIXTURES CAN BE DEFERRED SUBMITTALS BY REQUEST HOWEVER |
| PLEASE NOTE THE SUBMITTALS SHALL BEAR REVIEW AND |
| APPROVAL STAMPS BY THE DESIGN PROFESSIONAL AND BE |
| PROVIDED TO THE BUILDING DEPARTMENT PRIOR TO |
| INSTALLATION AND INSPECTIONS- SEC. 107.3.4.1 WPB. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |