Plan Review Notes
Plan Review Notes For Permit 22080258
Permit Number 22080258
Review Stop P
Sequence Number 2
Notes
Date Text
2022-11-18 17:22:472ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22080258
 11/18/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE COD
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3-00: COMPLIANCE WITH DISPERSION OF THE
 ACCESSIBLE UNITS WAS CALLED OUT IN 1ST REVIEW COMMENT
 #2B IN ACCORDANCE WITH SEC. 224.5 FBC ACC. THE UNIT
 MATRIX SUMMARY DOES NOT APPEAR TO SHOW COMPLIANCE WITH
 8 ADA STUDIO UNITS, 2 ADA 1-BED UNITS, AND 1 ADA 2-BED
 UNIT. PLEASE REVIEW SEC. 224.5-
 "GUEST ROOMS REQUIRED TO PROVIDE MOBILITY FEATURES
 COMPLYING WITH 806.2 AND GUEST ROOMS REQUIRED TO
 PROVIDE COMMUNICATION FEATURES COMPLYING WITH 806.3
 SHALL BE DISPERSED AMONG THE VARIOUS CLASSES OF GUEST
 ROOMS, AND SHALL PROVIDE CHOICES OF TYPES OF GUEST
 ROOMS, NUMBER OF BEDS, AND OTHER AMENITIES COMPARABLE
 TO THE CHOICES PROVIDED TO OTHER GUESTS."
  
 2) SHEET A3-00: THE MATRIX ADA SUITES MOBILITY LIST
 DESIGNATES STUDIO 740 AS A "FLORIDA ACCESSIBLE UNIT".
 THIS APPEARS TO BE A MISLABEL AND SHOULD INDICATE FAIR
 HOUSING COMPLIANCE BASED ON SHEET A3-19B WHICH SHOWS A
 TYPE B BATHROOM LAYOUT FOR UNIT 740- SEE PAGE 7.34 FAIR
 HOUSING DESIGN ACT MANUAL. PLEASE NOTE THAT ALL ADA
 SUITES SHALL ALSO BE DESIGNED AND CONSTRUCTED IN
 COMPLIANCE WITH THE FLORIDA ACCESSIBILITY CODE.
  
 3) SHEET A3-10A, UNIT 3A HC MISSING OR INCORRECT
 DETAILS PER FBC ACC.
 A) DETAIL 1: SHOW THE CLEAR FLOOR DEPTH MEASUREMENT AT
 THE WATER CLOSET- SEC. 604.3.
 B) DETAIL 1: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR A FORWARD APPROACH TO THE LAVATORY- SEC.
 606.2.
 C) DETAILS 6 & 8: SHOW THE KNEE AND TOE CLEARANCES FOR
 THE LAVATORY- SEC. 606.2 & FIGURES 306.2 & 306.3.
 D) DETAIL 8: SHOW THE HEIGHT OF THE WATER CLOSET WILL
 BE 17-IN. MIN. AND 19-IN. MAX. FROM THE FINISHED FLOOR
 TO THE TOP OF THE SEAT- SEC. 604.4.
 E) DETAIL 1 & 6: SHOW THE WATER CLOSET GRAB BAR LENGTHS
 AND SPACINGS PER FIGURES 694.5.1 & 604.5.2.
 F) DETAIL 1: SHOW THE 30 X 60 IN. CLEAR FLOOR SPACE
 DIAGRAM AT THE SHOWER- SEC. 608.2.2.1.
 G) DETAILS 1,7, 8: SHOW SHOWER GRAB BAR LENGTHS AND
 SPACINGS FROM ADJACENT WALLS- SEC. 608.3.2.
 H) DETAILS 7 & 8: SHOW THE ROLL-IN SHOWER THRESHOLD
 HEIGHT- SEC. 608.7.
 I) DETAIL 7: SHOW THE HEIGHT OF THE SHOWER SEAT FROM
 THE SHOWER FLOOR TO THE TOP OF THE SEAT- 610.2.
 J) PROVIDE DIMENSIONED TUB AND SHOWER SEAT DIAGRAMS AND
 INDICATE THE TUB SEAT IS REMOVABLE AND THE SHOWER SEAT
 IS A FOLDING TYPE- SEC. 610.3- 610.4.
  
 4) SHEET A3-15A, UNIT B2B HC MISSING OR INCORRECT
 DETAILS PER FBC ACC.
 A) DETAIL 1: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND
 DIMENSIONS FOR A FORWARD APPROACH TO THE LAVATORY- SEC.
 606.2
 B) DETAILS 6: SHOW THE KNEE AND TOE CLEARANCES FOR THE
 LAVATORY- SEC. 606.2 & FIGURES 306.2 & 306.3.
 C) DETAIL 6: SHOW THE HEIGHT OF THE WATER CLOSET WILL
 BE 17-IN. MIN. AND 19-IN. MAX. FROM THE FINISHED FLOOR
 TO THE TOP OF THE SEAT- SEC. 604.4.
 D) DETAIL 1 & 6: SHOW THE WATER CLOSET GRAB BAR LENGTHS
 AND SPACINGS PER FIGURES 694.5.1 & 604.5.2.
 E) DETAIL 1: SHOW THE CLEAR WIDTH AND DEPTH
 MEASUREMENTS OF THE WALK-IN SHOWER, AND THE 36 X 48 IN.
 CLEAR FLOOR SPACE ENTRY ON THE FACE OF THE COMPARTMENT
 MEASURED FROM THE CONTROL WALL- SEC. 608.2.1.
 F) DETAILS 1,7, 8: SHOW SHOWER GRAB BAR LENGTHS AND
 SPACINGS FROM ADJACENT WALLS- SEC. 608.3.1.
 G) DETAIL 8: SHOW THE SHOWER CONTROLS, FAUCET, AND
 SPRAY SHALL BE LOCATED ON THE CONTROL WALL 15-INCHES
 MAXIMUM FROM THE CENTERLINE OF THE SEAT TOWARD THE
 SHOWER OPENING.
 H) DETAIL 7: SHOW THE HEIGHT OF THE SHOWER SEAT FROM
 THE SHOWER FLOOR TO THE TOP OF THE SEAT- 610.2
 I) DETAIL 6: PROVIDE A DIMENSIONED SHOWER SEAT DIAGRAM
 AND INDICATE THE SHOWER SEAT IS A FOLDING TYPE- SEC.
 610.3- 610.4.
  
 5) SHEET A3-19A, UNIT E1F.4HC MISSING OR INCORRECT
 DETAILS PER FBC ACC: PLEASE SEE COMMENT #3 ABOVE FOR
 SIMILAR DEFICIENCIES AND PROVIDE CORRECTIONS- SEC.
 107.2.1 WPB.
  
 6) SHEET A3-29A, UNIT E2G.1 MISSING OR INCORRECT
 DETAILS PER FBC ACC: PLEASE REVIEW COMMENT #2 FOR
 SIMILAR DEFICIENCIES AND PROVIDE CORRECTIONS- SEC.
 107.2.1 WPB.
  
 7) SHEET A3-19B, UNIT E1F.4 FAIR HOUSING COMPLIANCE.
 A) DETAILS 1, 3 & 5: PLEASE SHOW THE LENGTHS OF THE
 WATER CLOSET GRAB BARS- PAGE 6.5 FAIR HOUSING DESIGN
 ACT MANUAL.
  
 8) SHEETS A-3-10A, A3-15A, A3-19A, A3-19B, A3-29A: THE
 CLEAR FLOOR SPACE DIAGRAM POSITIONED FOR A FORWARD
 APPROACH TO THE KITCHEN SINK DOES NOT APPEAR TO INCLUDE
 THE REQUIRED KNEE AND TOE CLEARANCES. PLEASE CLARIFY IF
 THE CABINETS ARE DESIGNED TO ALLOW THE CLEARANCES FOR A
 FORWARD APPROACH OR PROVIDE A PARALLEL APPROACH- SEC.
 606.2 FBC ACC.
  
 9) SHEETS P3-15A & P-15 DETAIL 4: SHOW THE WASHING
 MACHINE DRAIN CONNECTION TO THE WASTE STACK- SEC. 913.2
 FBC P.
  
 10) 2ND REQUEST. SHEETS P1-01B & P4-01: PROVIDE THE
 MAKES AND MODELS OF THE FACILITY WASHING MACHINES AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS- SECS. 406.1 &
 406.2 FBC P. THE MACHINES MUST DISCHARGE BY GRAVITY,
 AND LINT INTERCEPTORS ARE REQUIRED- SEC. 1003.6 FBC P.
 REVISE THE PIPING DRAWING TO SHOW THE LOCATION AND
 PIPING CONNECTIONS TO THE INTERCEPTOR.
  
 11) 2ND REQUEST TO PROVIDE WATER RISER DRAWINGS.
 DRAWINGS ARE PROVIDED FOR THE INDIVIDUAL UNITS HOWEVER
 RISERS NOT PROVIDE FOR THE LAUNDRY ROOM AND THE THE
 PIPING TO THE 24 FACILITY WATER HEATERS SHOWN IN THE
 GAS RISER- SEC. 107.3.5.1.3 WPB.
  
 12) PLEASE PROVIDE A FLOOR PLAN DRAWING SIMILAR TO
 SHEET P1-01B THAT SHOWS THE LOCATIONS OF THE 24- GAS
 WATER HEATERS AND GAS AND WATER PIPING LAYOUTS- SEC.
 107.2.1 WPB.
  
 13) PLEASE SHOW COMPLIANCE ON THE PLANS WITH SEC.
 607.1.1 FBC P AND PROVIDE MASTER THERMOSTATIC MIXING
 VALVES AT THE WATER HEATER IN THE LAUNDRY ROOM AND FOR
 THE FACILITY WATER HEATERS.
  
 14) P4-01: THE PLUMBING FIXTURE SCHEDULES IS MISSING
 MANY ITEMS INCLUDING THE KITCHEN SINKS, DISHWASHERS,
 KITCHEN AND LAVATORY FAUCETS, SHOWER VALVES AND FAUCETS
 AND SPRAYS, TUB AND SHOWER VALVES AND FAUCETS, AND
 WASHING MACHINES- SEC. 107.2.1 WPB. THE SCHEDULE ALSO
 LISTS ONLY ONE ADA COMPLIANT SHOWER AND THERE IS A
 WALK-IN AND ROLL-IN TYPE. PLEASE PROVIDE A COMPLETE
 FIXTURE SCHEDULE AND AS PREVIOUSLY REQUESTED SUBMIT
 SPECS FOR THE ADA SHOWERS. THE SHOWERS AND OTHER
 FIXTURES CAN BE DEFERRED SUBMITTALS BY REQUEST HOWEVER
 PLEASE NOTE THE SUBMITTALS SHALL BEAR REVIEW AND
 APPROVAL STAMPS BY THE DESIGN PROFESSIONAL AND BE
 PROVIDED TO THE BUILDING DEPARTMENT PRIOR TO
 INSTALLATION AND INSPECTIONS- SEC. 107.3.4.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  