Plan Review Notes
Plan Review Notes For Permit 22080258
Permit Number 22080258
Review Stop G
Sequence Number 2
Notes
Date Text
2022-11-21 08:32:542ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 22080258
 11/21/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2-01 GAS RISER: SHOW THE PIPE SIZE FROM THE
 REGULATOR TO GWH-1 AT THE LAUNDRY- TABLE 402.4(3).
  
 2) P1-01B & P2-01: 2ND REQUEST TO PROVIDE COMBUSTION
 AIR AND VENTING PLANS FOR THE GAS WATER HEATERS- SECS.
 304.1, 503.1 & 624.1.FBC FG. THE ARCHITECT???S RESPONSE
 INDICATES THE DETAILS ARE ON THE MECHANICAL PLANS
 HOWEVER THEY ARE NOT PROVIDED THERE.
 A) 2ND REQUEST TO PROVIDE MANUFACTURER???S
 SPECIFICATIONS FOR THE WATER HEATERS.
 B) PLEASE PROVIDE A FLOOR PLAN DRAWING SIMILAR TO SHEET
 P1-01B THAT SHOWS THE LOCATIONS OF THE 24- GAS WATER
 HEATERS AND GAS AND WATER PIPING LAYOUTS- SEC. 107.2.1
 WPB.
  
 3) P1-01B & P2-01: 2ND REQUEST TO PROVIDE COMBUSTION
 AIR AND VENTING PLANS FOR THE GAS DRYERS- SECS. 304.1,
 614.1 & 614.4 FBC FG. THE ARCHITECT???S RESPONSE
 INDICATES THE DETAILS ARE ON THE MECHANICAL PLANS
 HOWEVER ONLY TWO 8-INCH VENTS ARE SHOWN ON M1-02B.
 THERE IS A NOTE ON THE PLAN REFERENCING THE SUBMITTED
 MANUFACTURER???S SPECIFICATIONS, HOWEVER THE COMBUSTION
 AIR AND VENTING INFORMATION (PAGE 37) IS NOT CONTAINED
 IN THE DOCUMENT.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS ST.
 WEST PALM BEACH, FL. 33401
 561-805-6719
 [email protected]
  
  