2022-08-26 14:19:57 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22080258 |
| 8/26/22 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) DESIGN CRITERIA: PLEASE PROVIDE CODE DATA AND A |
| SCOPE OF WORK ON THE PLANS FOR THE PROJECT- SEC.107.2.1 |
| WPB. THE PLANS APPEAR TO SHOW THE PREVIOUS |
| NON-TRANSIENT R2 OCCUPANCY IS BEING CONVERTED TO A R1 |
| NON-TRANSIENT HOTEL OCCUPANCY- SEC. 310.3 & 310.4 FBC |
| B. BASED ON SEC.1006.1 FBC EX, BUILDINGS UNDERGOING A |
| CHANGE OF OCCUPANCY SHALL COMPLY WITH THE FBC |
| ACCESSIBILITY CODE. |
| |
| 2) SHEET A-300: CONCERNING THE PLUMBING FIXTURES IN THE |
| ALTERED KITCHENS AND BATHS PLEASE REVIEW THE FOLLOWING |
| FBC ACC CODE SECTIONS AND PROVIDE A SUMMARY ON THE |
| PLAN. |
| A) SECS 224.1 & 224.1.1: INDICATE THE NUMBER OF GUEST |
| ROOMS TO BE PROVIDED WITH MOBILITY FEATURES COMPLYING |
| WITH SEC. 806.2. |
| B) 224.5: SHOW COMPLIANCE WITH DISPERSION OF THE |
| ACCESSIBLE UNITS WITH MOBILITY FEATURES. |
| C) TABLE 224.2: SHOW COMPLIANCE FOR THE MINIMUM NUMBER |
| OF ROOMS WITH OR WITHOUT ROLL-IN SHOWERS. |
| |
| 3) SHEETS A3-10A, A3-15A, A3-19A, A3-29A: PROVIDE THE |
| FOLLOWING LIST OF COMPLIANCE DETAILS PER THE FBC ACC: |
| A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS- |
| SEC. 604.3. |
| B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES- |
| SEC. 606.2. |
| C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| FLOORS- SEC. 604.4. |
| E) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| THE REFLECTIVE SURFACES- SEC. 603.3 |
| F) LENGTHS OF THE SIDE WALL AND REAR GRAB BARS FOR THE |
| WATER CLOSETS- SEC. 604.5. |
| G) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC. |
| 604.6. |
| H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES AND |
| KITCHEN SINKS- SECTION 606.2. |
| I) BATHTUB DIMENSIONS, AND CLEAR FLOOR SPACE |
| DIMENSIONS- SEC. 607.2. |
| J) DIMENSIONS OF TRANSFER TYPE SHOWERS (36X36 INCHES)- |
| SEC. 608.2.1 |
| K) DIMENSIONS OF THE ROLL-IN SHOWERS- SEC. 608.2.2. |
| L) DIMENSIONS OF THE CLEAR FLOOR SPACES FOR EACH TYPE |
| OF SHOWER- SECS. 608.2.1 & 608.2.2. |
| M) LENGTHS AND SPACING OF GRAB BARS FOR THE ACCESSIBLE |
| SHOWERS- SECS. 608.3.1 & 608.3.2. |
| N) LOCATIONS OF CONTROL, FAUCET, AND SHOWER SPRAYS IN |
| THE SHOWERS- SECS. 608.5.1 & 608.5.2. |
| O) BATHTUB AND SHOWER SEAT DETAILS BASED ON SECS. |
| 610.2- 610.3.2. |
| |
| 4) SHEETS A3-10A, A3-19A, A3-29A: PLUMBING PIPING PLANS |
| AND ISOMETRIC DRAWINGS ARE REQUIRED FOR THE ALTERED |
| UNITS- SEC. 107.2.1 & 107.3.5.1.3 WPB. |
| |
| 5) SHEET P1-01B: PROVIDE PLUMBING RISER DRAWINGS- SEC. |
| 107.3.5.1.3 WPB. |
| |
| 6) SHEETS P1-01B & P4-01: PROVIDE THE MAKES AND MODELS |
| OF THE WASHING MACHINES AND SUBMIT MANUFACTURER'S |
| SPECIFICATIONS- SECS. 406.1 & 406.2 FBC P. THE MACHINES |
| MUST DISCHARGE BY GRAVITY, AND INTERCEPTORS ARE |
| REQUIRED- SEC. 1003.6 FBC P. |
| |
| 7) P4-01: PROVIDE THE MAKES AND MODELS OF THE ADA |
| COMPLIANT SHOWERS AND SUBMIT MANUFACTURER'S |
| SPECIFICATIONS. THE UNITS MUST BE IN COMPLIANCE WITH |
| SEC. 421.1 FBC P. AND SEC. 608.1 FBC ACC. PLEASE NOTE |
| THAT THRESHOLDS FOR THE ROLL-IN SHOWER SHALL BE MAXIMUM |
| 1/2--INCH HIGH- SEC. 608.7 FBC ACC. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |