Plan Review Notes
Plan Review Notes For Permit 22080258
Permit Number 22080258
Review Stop P
Sequence Number 1
Notes
Date Text
2022-08-26 14:19:571ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22080258
 8/26/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DESIGN CRITERIA: PLEASE PROVIDE CODE DATA AND A
 SCOPE OF WORK ON THE PLANS FOR THE PROJECT- SEC.107.2.1
 WPB. THE PLANS APPEAR TO SHOW THE PREVIOUS
 NON-TRANSIENT R2 OCCUPANCY IS BEING CONVERTED TO A R1
 NON-TRANSIENT HOTEL OCCUPANCY- SEC. 310.3 & 310.4 FBC
 B. BASED ON SEC.1006.1 FBC EX, BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY SHALL COMPLY WITH THE FBC
 ACCESSIBILITY CODE.
  
 2) SHEET A-300: CONCERNING THE PLUMBING FIXTURES IN THE
 ALTERED KITCHENS AND BATHS PLEASE REVIEW THE FOLLOWING
 FBC ACC CODE SECTIONS AND PROVIDE A SUMMARY ON THE
 PLAN.
 A) SECS 224.1 & 224.1.1: INDICATE THE NUMBER OF GUEST
 ROOMS TO BE PROVIDED WITH MOBILITY FEATURES COMPLYING
 WITH SEC. 806.2.
 B) 224.5: SHOW COMPLIANCE WITH DISPERSION OF THE
 ACCESSIBLE UNITS WITH MOBILITY FEATURES.
 C) TABLE 224.2: SHOW COMPLIANCE FOR THE MINIMUM NUMBER
 OF ROOMS WITH OR WITHOUT ROLL-IN SHOWERS.
  
 3) SHEETS A3-10A, A3-15A, A3-19A, A3-29A: PROVIDE THE
 FOLLOWING LIST OF COMPLIANCE DETAILS PER THE FBC ACC:
 A) CLEAR FLOOR SPACE DIMENSIONS FOR THE WATER CLOSETS-
 SEC. 604.3.
 B) CLEAR FLOOR SPACE DIMENSIONS FOR THE LAVATORIES-
 SEC. 606.2.
 C) TURNING SPACE DIAMETERS- SEC. 304.3.
 D) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SEC. 604.4.
 E) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SEC. 603.3
 F) LENGTHS OF THE SIDE WALL AND REAR GRAB BARS FOR THE
 WATER CLOSETS- SEC. 604.5.
 G) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- SEC.
 604.6.
 H) KNEE AND TOE CLEARANCES FOR THE LAVATORIES AND
 KITCHEN SINKS- SECTION 606.2.
 I) BATHTUB DIMENSIONS, AND CLEAR FLOOR SPACE
 DIMENSIONS- SEC. 607.2.
 J) DIMENSIONS OF TRANSFER TYPE SHOWERS (36X36 INCHES)-
 SEC. 608.2.1
 K) DIMENSIONS OF THE ROLL-IN SHOWERS- SEC. 608.2.2.
 L) DIMENSIONS OF THE CLEAR FLOOR SPACES FOR EACH TYPE
 OF SHOWER- SECS. 608.2.1 & 608.2.2.
 M) LENGTHS AND SPACING OF GRAB BARS FOR THE ACCESSIBLE
 SHOWERS- SECS. 608.3.1 & 608.3.2.
 N) LOCATIONS OF CONTROL, FAUCET, AND SHOWER SPRAYS IN
 THE SHOWERS- SECS. 608.5.1 & 608.5.2.
 O) BATHTUB AND SHOWER SEAT DETAILS BASED ON SECS.
 610.2- 610.3.2.
  
 4) SHEETS A3-10A, A3-19A, A3-29A: PLUMBING PIPING PLANS
 AND ISOMETRIC DRAWINGS ARE REQUIRED FOR THE ALTERED
 UNITS- SEC. 107.2.1 & 107.3.5.1.3 WPB.
  
 5) SHEET P1-01B: PROVIDE PLUMBING RISER DRAWINGS- SEC.
 107.3.5.1.3 WPB.
  
 6) SHEETS P1-01B & P4-01: PROVIDE THE MAKES AND MODELS
 OF THE WASHING MACHINES AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SECS. 406.1 & 406.2 FBC P. THE MACHINES
 MUST DISCHARGE BY GRAVITY, AND INTERCEPTORS ARE
 REQUIRED- SEC. 1003.6 FBC P.
  
 7) P4-01: PROVIDE THE MAKES AND MODELS OF THE ADA
 COMPLIANT SHOWERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS. THE UNITS MUST BE IN COMPLIANCE WITH
 SEC. 421.1 FBC P. AND SEC. 608.1 FBC ACC. PLEASE NOTE
 THAT THRESHOLDS FOR THE ROLL-IN SHOWER SHALL BE MAXIMUM
 1/2--INCH HIGH- SEC. 608.7 FBC ACC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  