2022-08-26 14:46:16 | 1ST REVIEW FBC-2020 FUEL GAS |
| PERMIT- 22080258 |
| 8/26/22 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P1-01B: PROVIDE A COMPLETE GAS RISER THAT |
| INCLUDES THE NEW GAS PIPING TO THE WATER HEATER AND |
| DRYERS, AND ALL EXISTING GAS PIPING AND APPLIANCES- |
| SECS. 402.1 & 402.2 FBC FG. PLEASE INCLUDE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS INCLUDING |
| THE PIPE SUPPLYING THE WATER HEATER. |
| G) LOCATIONS OF REGULATORS AND SHUT OFF VALVES. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) P1-01B GAS WATER HEATER- FBC FG. |
| A) PROVIDE AN EQUIPMENT SCHEDULE AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS- SEC. 624.1. |
| B) PROVIDE COMBUSTION AIR AND VENTING PLANS- SECS. |
| 304.1, 503.1 & 624.1. |
| |
| 3) P1-01B GAS DRYERS- FBC FG. |
| A) PROVIDE AN EQUIPMENT SCHEDULE AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS- SEC. 613.1. |
| B) PROVIDE COMBUSTION AIR AND EXHAUST PLANS- SECS. |
| 304.1, 614.1 & 614.4. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |