Plan Review Notes
Plan Review Notes For Permit 22080258
Permit Number 22080258
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-08-17 15:17:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF CO DETECTORS WITHIN THIS
 NEW HOTEL OCCUPANCY.
  
 PER NFPA 101 CH 28
  
 28.3.4.7 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE
 DETECTION SYSTEMS.
  
 28.3.4.7.1 CARBON MONOXIDE ALARMS OR CARBON MONOXIDE
 DETECTORS IN
 ACCORDANCE WITH SECTION 9.12 AND 28.3.4.7 SHALL BE
 PROVIDED IN NEW
 HOTELS AND DORMITORIES WHERE EITHER OF THE FOLLOWING
 CONDITIONS EXISTS:
 (1) GUEST ROOMS OR GUEST SUITES WITH COMMUNICATING
 ATTACHED GARAGES,
 UNLESS OTHERWISE EXEMPTED BY 28.3.4.7.3
 (2) GUEST ROOMS OR GUEST SUITES CONTAINING A
 PERMANENTLY INSTALLED
 FUEL-BURNING APPLIANCE OR FUEL-BURNING FIREPLACE
  
 28.3.4.7.2 WHERE REQUIRED BY 28.3.4.7, CARBON MONOXIDE
 ALARMS OR
 CARBON MONOXIDE DETECTORS SHALL BE INSTALLED IN THE
 FOLLOWING
 LOCATIONS:
 (1) OUTSIDE OF EACH SEPARATE GUEST ROOM OR GUEST SUITE
 SLEEPING AREA
 IN THE IMMEDIATE VICINITY OF THE SLEEPING ROOMS
 (2) ON EVERY OCCUPIABLE LEVEL OF A GUEST ROOM AND GUEST
 SUITE
  
  
 28.3.4.7.3 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE
 DETECTORS AS
 SPECIFIED IN 28.3.4.7.1(1) SHALL NOT BE REQUIRED IN THE
 FOLLOWING
 LOCATIONS:
 (1) IN GARAGES
 (2) WITHIN GUEST ROOMS OR GUEST SUITES WITH
 COMMUNICATING ATTACHED
 GARAGES THAT ARE OPEN PARKING STRUCTURES AS DEFINED BY
 THE BUILDING
 CODE
 (3) WITHIN GUEST ROOMS OR GUEST SUITES WITH
 COMMUNICATING ATTACHED
 GARAGES THAT ARE MECHANICALLY VENTILATED IN ACCORDANCE
 WITH THE
 MECHANICAL CODE
  
 PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS AND
 SPECIFIC REFERNCES OF OMISSION.
  
  
 2) THERE ARE NO INDICATIONS OF FIRE SPRINKLER COMPIANCE
 AND OR EVALUATION FROM APARTMENT BUILDING VS HOTEL.
  
 PER NFPA 101 CH 28
  
 28.3.5 EXTINGUISHMENT REQUIREMENTS.
 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH 28.3.5.3.
  
 28.3.5.3 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR
 TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE
 IN ACCORDANCE WITH
 SECTION 9.7, AS MODIFIED BY 28.3.5.4. IN HOTEL OR
 DORMITORY OCCUPANCIES
 UP TO AND INCLUDING FOUR STORIES IN HEIGHT THAT ARE
 LOCATED-IN BUILDINGS
 NOT EXCEEDING 60 FT (18.3 M) IN HEIGHT ABOVE GRADE
 PLANE, SYSTEMS IN
 ACCORDANCE WITH NFPA 13R SHALL BE PERMITTED
  
 28.3.5.6 LISTED QUICK-RESPONSE OR LISTED RESIDENTIAL
 SPRINKLERS SHALL BE
 USED THROUGHOUT GUEST ROOMS AND GUEST ROOM SUITES
  
 PLEASE PROVIDE A REVIEW OF COMPLIANCE FROM A QUALIFIED
 FIRE SPRINKLER CONTRACTOR WITH A NOTE OF ACKNOWLEGMENT
 TO COMPLY WITH SHOP DRAWINGS PROVIDED UNDER SEPARATE
 PERMIT.
  
  
 3) THERE ARE NO INDICATIONS OF EMERGENCY INSTRUCTIONS
  
 PER NFPA 101 CH 28
  
 28.7.4 EMERGENCY INSTRUCTIONS FOR RESIDENTS OR GUESTS.
 28.7.4.1* A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR
 ARRANGEMENT, EXIT
 LOCATIONS, AND ROOM IDENTIFICATION SHALL BE POSTED IN A
 LOCATION AND
 MANNER ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION
 ON, OR IMMEDI ATELY ADJACENT TO, EVERY GUEST ROOM DOOR
 IN HOTELS AND IN EVERY RESIDENT
 ROOM IN DORMITORIES
  
 PLEASE REVIEW AND PROVIDE A DRAFT FOR REVIEW AND THE
 PROPOSED LOCATIONS(S)
  
  
  
 4) THERE IS NO DOOR SCHEDULE INDICATING THE UNITS
 LOCKING AND LATCHING PER NFPA 101 CH 7
  
 28.2.2.2 DOORS.
 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 PLEASE PROVIDE FOR ANY CHANGES TO THE DOOR HARDWARE
 LOCKING AND LATCHING AND OR PROVIDE A NOTE OF NO
 CHANGES.
  
  
  
 5) THERE ARE NO INDICATIONS OF ANY CHANGES TO THE
 ACCESS CONTROL OF THIS HOTEL OCCUPANCY.
  
 28.2.2.2.2.2 DELAYED-EGRESS ELECTRICAL LOCKING SYSTEMS
 COMPLYING WITH
 7.2.1.6.1 SHALL BE PERMITTED.
 28.2.2.2.2.3 SENSOR-RELEASE OF ELECTRICAL LOCKING
 SYSTEMS COMPLYING
 WITH 7.2.1.6.2 SHALL BE PERMITTED
  
 ANY CHANGES TO THE ACCESS CONTROL SHALL BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEGMENT IF APPLICABLE.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  