2022-08-17 15:17:18 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE ARE NO INDICATIONS OF CO DETECTORS WITHIN THIS |
| NEW HOTEL OCCUPANCY. |
| |
| PER NFPA 101 CH 28 |
| |
| 28.3.4.7 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE |
| DETECTION SYSTEMS. |
| |
| 28.3.4.7.1 CARBON MONOXIDE ALARMS OR CARBON MONOXIDE |
| DETECTORS IN |
| ACCORDANCE WITH SECTION 9.12 AND 28.3.4.7 SHALL BE |
| PROVIDED IN NEW |
| HOTELS AND DORMITORIES WHERE EITHER OF THE FOLLOWING |
| CONDITIONS EXISTS: |
| (1) GUEST ROOMS OR GUEST SUITES WITH COMMUNICATING |
| ATTACHED GARAGES, |
| UNLESS OTHERWISE EXEMPTED BY 28.3.4.7.3 |
| (2) GUEST ROOMS OR GUEST SUITES CONTAINING A |
| PERMANENTLY INSTALLED |
| FUEL-BURNING APPLIANCE OR FUEL-BURNING FIREPLACE |
| |
| 28.3.4.7.2 WHERE REQUIRED BY 28.3.4.7, CARBON MONOXIDE |
| ALARMS OR |
| CARBON MONOXIDE DETECTORS SHALL BE INSTALLED IN THE |
| FOLLOWING |
| LOCATIONS: |
| (1) OUTSIDE OF EACH SEPARATE GUEST ROOM OR GUEST SUITE |
| SLEEPING AREA |
| IN THE IMMEDIATE VICINITY OF THE SLEEPING ROOMS |
| (2) ON EVERY OCCUPIABLE LEVEL OF A GUEST ROOM AND GUEST |
| SUITE |
| |
| |
| 28.3.4.7.3 CARBON MONOXIDE ALARMS AND CARBON MONOXIDE |
| DETECTORS AS |
| SPECIFIED IN 28.3.4.7.1(1) SHALL NOT BE REQUIRED IN THE |
| FOLLOWING |
| LOCATIONS: |
| (1) IN GARAGES |
| (2) WITHIN GUEST ROOMS OR GUEST SUITES WITH |
| COMMUNICATING ATTACHED |
| GARAGES THAT ARE OPEN PARKING STRUCTURES AS DEFINED BY |
| THE BUILDING |
| CODE |
| (3) WITHIN GUEST ROOMS OR GUEST SUITES WITH |
| COMMUNICATING ATTACHED |
| GARAGES THAT ARE MECHANICALLY VENTILATED IN ACCORDANCE |
| WITH THE |
| MECHANICAL CODE |
| |
| PLEASE REVIEW AND CORRECT OR PROVIDE DETAILS AND |
| SPECIFIC REFERNCES OF OMISSION. |
| |
| |
| 2) THERE ARE NO INDICATIONS OF FIRE SPRINKLER COMPIANCE |
| AND OR EVALUATION FROM APARTMENT BUILDING VS HOTEL. |
| |
| PER NFPA 101 CH 28 |
| |
| 28.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 28.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH 28.3.5.3. |
| |
| 28.3.5.3 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| INSTALLED, EITHER FOR |
| TOTAL OR PARTIAL BUILDING COVERAGE, THE SYSTEM SHALL BE |
| IN ACCORDANCE WITH |
| SECTION 9.7, AS MODIFIED BY 28.3.5.4. IN HOTEL OR |
| DORMITORY OCCUPANCIES |
| UP TO AND INCLUDING FOUR STORIES IN HEIGHT THAT ARE |
| LOCATED-IN BUILDINGS |
| NOT EXCEEDING 60 FT (18.3 M) IN HEIGHT ABOVE GRADE |
| PLANE, SYSTEMS IN |
| ACCORDANCE WITH NFPA 13R SHALL BE PERMITTED |
| |
| 28.3.5.6 LISTED QUICK-RESPONSE OR LISTED RESIDENTIAL |
| SPRINKLERS SHALL BE |
| USED THROUGHOUT GUEST ROOMS AND GUEST ROOM SUITES |
| |
| PLEASE PROVIDE A REVIEW OF COMPLIANCE FROM A QUALIFIED |
| FIRE SPRINKLER CONTRACTOR WITH A NOTE OF ACKNOWLEGMENT |
| TO COMPLY WITH SHOP DRAWINGS PROVIDED UNDER SEPARATE |
| PERMIT. |
| |
| |
| 3) THERE ARE NO INDICATIONS OF EMERGENCY INSTRUCTIONS |
| |
| PER NFPA 101 CH 28 |
| |
| 28.7.4 EMERGENCY INSTRUCTIONS FOR RESIDENTS OR GUESTS. |
| 28.7.4.1* A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR |
| ARRANGEMENT, EXIT |
| LOCATIONS, AND ROOM IDENTIFICATION SHALL BE POSTED IN A |
| LOCATION AND |
| MANNER ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION |
| ON, OR IMMEDI ATELY ADJACENT TO, EVERY GUEST ROOM DOOR |
| IN HOTELS AND IN EVERY RESIDENT |
| ROOM IN DORMITORIES |
| |
| PLEASE REVIEW AND PROVIDE A DRAFT FOR REVIEW AND THE |
| PROPOSED LOCATIONS(S) |
| |
| |
| |
| 4) THERE IS NO DOOR SCHEDULE INDICATING THE UNITS |
| LOCKING AND LATCHING PER NFPA 101 CH 7 |
| |
| 28.2.2.2 DOORS. |
| 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| |
| PLEASE PROVIDE FOR ANY CHANGES TO THE DOOR HARDWARE |
| LOCKING AND LATCHING AND OR PROVIDE A NOTE OF NO |
| CHANGES. |
| |
| |
| |
| 5) THERE ARE NO INDICATIONS OF ANY CHANGES TO THE |
| ACCESS CONTROL OF THIS HOTEL OCCUPANCY. |
| |
| 28.2.2.2.2.2 DELAYED-EGRESS ELECTRICAL LOCKING SYSTEMS |
| COMPLYING WITH |
| 7.2.1.6.1 SHALL BE PERMITTED. |
| 28.2.2.2.2.3 SENSOR-RELEASE OF ELECTRICAL LOCKING |
| SYSTEMS COMPLYING |
| WITH 7.2.1.6.2 SHALL BE PERMITTED |
| |
| ANY CHANGES TO THE ACCESS CONTROL SHALL BE INSTALLED |
| UNDER SEPARATE PERMIT AND SHOP DRAWINGS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEGMENT IF APPLICABLE. |
| |
| |
| |
| 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |