2022-09-15 16:16:53 | CHANGE OF OCCUPANCY |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) ON THE DRAWINGS PLEASE SHOW THAT THIS IS A CHANGE OF |
| OCCUPANCY CLASSIFICATION (SHOW EXISTING OCCUPANCY |
| CLASSIFICATION AND NEW OCCUPANCY CLASSIFICATION) FBC |
| EXISTING 1012 |
| 2) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE ??? FBC |
| 602.1 |
| 3) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE SLIDING GLASS DOORS ??? ALL |
| PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE DESIGNER OF RECORD FBC WPB 107.3.4 |
| 4) PLEASE PROVIDE THE WIND DESIGN PRESSURES FOR THE |
| OPENINGS WHERE THE SLIDING GLASS DOORS ARE BEING |
| REPLACED FBC 1609 |
| 5) PLEASE NOTE ON THE DRAWINGS THE REQUIRED INTERIOR |
| FINISHES FIRE CLASSIFICATION PER FBC TABLE 803.11 (FBC |
| EXISTING BUILDING 1012.3 INTERIOR FINISH. |
| IN AREAS OF THE BUILDING UNDERGOING THE CHANGE OF |
| OCCUPANCY CLASSIFICATION, THE INTERIOR FINISH OF WALLS |
| AND CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING FOR THE NEW OCCUPANCY |
| CLASSIFICATION. |
| 6) THERE IS DRAWING CD-23 FOR THE COMMON AND PUBLIC |
| AREA ??? THERE IS DRAWING CD-24 PERTAINING TO FHA WHICH |
| IS NOT REQUIRED FOR A HOTEL OCCUPANCY ??? THERE SHOULD |
| BE A DRAWING DETAILING THE ACCESSIBLE GUEST ROOMS PER |
| FBC ACCESSIBILITY. |
| 7) THE POOL WILL NEED TO MEET FBC ACCESSIBILITY 242 ??? |
| FBC E 1012.1.4 ACCESSIBILITY. |
| ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8. FBC |
| 1012.8 ACCESSIBILITY. |
| EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR |
| OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE |
| PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| |