2023-01-24 16:03:59RESIDENTIAL (R3) FOURTH BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22080253
 8403 IRONHORSE CT.
  
 NOTE:
 NEED TO ADDRESS THE SIGNATURE REVIEW ALSO. SEE COMENT
 AT THE BOTTOM OF THIS PAGE.
  
  
 2- ACCORDING SHUTTERS:
  
 PREVIOUS COMMENT:
 A) SHUTTERS INSTALLATION SCHEDULE SPECIFY CONCRETE AS
 THE SUBSTRATE WHERE SHUTTERS ARE GOING TO BE INSTALLED
 (TOP AND BOTTOM). TYPICALLY THE BOTTOM OF WINDOW
 OPENINGS IS CONCRETE BLOCK. REVISE INSTALLATION
 SCHEDULE USING THE ANCHOR FOR CONCRETE BLOCK SUBSTRATE
 AT THE BOTTOM OR PROVIDE PROOF SHOWING BOTTOM OF
 OPENINGS HAS POURED CONCRETE WITH THE STRENGTH
 SPECIFIED ON ANCHOR SCHEDULE OF PRODUCT APPROVAL
 SUBMITTED.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NOTE:
 ACCORDION SHUTTERS SCHEDULE UPLOADED TO PROJECTDOX ON
 1/6/2023 IS MISMATCHING THE ACCORDIGN SHUTTERS AND THE
 ARMOR SCREEN SHUTTERS INFORMATION. THE TOP FORM OF THE
 THIS SHUTTER SCHEDULE IS SPECIFYING FOLDING SHUTTER
 CORPORATION SHUTTERS BUT THE ACTUAL INSTALLATION
 SCHEDULE BELOW IS SHOWING THE 8 OPENINGS TO BE COVERED
 WITH THE ARMOR SCREEN SHUTTERS NOT THE 18 OPENINGS WITH
 ACCORDING SHUTTERS.
 THIS IS WHY THERE IS SO MUCH CONFUSION.
 THE ACTUAL REVISED ACCORDION SHUTTERS INSTALLATION
 SCHEDULE WAS NEVER UPLOADED. IN ORDER TO AVOID MORE
 CONFLICTS AND DEALYS, PLEASE UPLOAD THE REVISED
 ACCORDING SHUTTERS INSTALLATION SCHEDULE ADDRESING THE
 COMMENTS.
  
 PREVIOUS COMMENT:
 B) REVISE SHUTTER GLASS SEPARATION SPECIFIED ON SHUTTER
 INSTALLATION SCHEDULE FOR OPENINGS WITH A SHUTTER SPAN
 LONGER THAN 99 INCHES. SEE SHEET 13 OF 13 OF SHUTTERS
 PRODUCT APPROVAL AND REVISE AS REQUIRED. NEED 3-1/2
 INCH GLASS SEPARATION.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NOTE:
 ACCORDION SHUTTERS SCHEDULE UPLOADED TO PROJECTDOX ON
 1/6/2023 IS MISMATCHING THE ACCORDIGN SHUTTERS AND THE
 ARMOR SCREEN SHUTTERS INFORMATION. THE TOP FORM OF THE
 THIS SHUTTER SCHEDULE IS SPECIFYING FOLDING SHUTTER
 CORPORATION SHUTTERS BUT THE ACTUAL INSTALLATION
 SCHEDULE BELOW IS SHOWING THE 8 OPENINGS TO BE COVERED
 WITH THE ARMOR SCREEN SHUTTERS NOT THE 18 OPENINGS WITH
 ACCORDING SHUTTERS.
 THIS IS WHY THERE IS SO MUCH CONFUSION.
 THE ACTUAL REVISED ACCORDION SHUTTERS INSTALLATION
 SCHEDULE WAS NEVER UPLOADED. IN ORDER TO AVOID MORE
 CONFLICTS AND DEALYS, PLEASE UPLOAD THE REVISED
 ACCORDING SHUTTERS INSTALLATION SCHEDULE ADDRESING THE
 COMMENTS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
 SIGNATURE REVIEW:
  
 THOMAS J. TWOMEY P.E DWG 1 OF 1 SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL320-R10 NEEDS ORIGINAL
 SEAL/SIGNATURE AS REQUIRED BY CHAPTER 471 F.S. WHEN
 SUBMITTING FOR PUBLIC RECORDS.
  
 NOTE: UPLOAD THIS DRAWING IN THE DRAWINGS FOLDER.
  
  
  