2022-09-21 13:33:00 | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. PAGE P101 - 2020 FPC 1002.1 FIXTURE TRAPS - THE | | FLOOR DRAINS ARE REQUIRED TO HAVE P-TRAPS. | | | | 2. 2020 914.1 CIRCUIT VENT PERMITTED - THE FIXTURE | | DRAINS OF THE FIXTURES BEING CIRCUIT VENTED SHALL | | CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH DRAIN | | BEING CIRCUIT VENTED. CANNOT CONNECT VERTICALLY. | | | | 3. 2020 FPC 1002.4.1 TRAP SEAL PROTECTION - TRAPS | | SUBJECT TO EVAPORATION ARE REQUIRED TO HAVE PROTECTION. | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] |
|