Plan Review Notes
Plan Review Notes For Permit 22080231
Permit Number 22080231
Review Stop P
Sequence Number 1
Notes
Date Text
2022-09-21 13:33:001ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
  
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. PAGE P101 - 2020 FPC 1002.1 FIXTURE TRAPS - THE
 FLOOR DRAINS ARE REQUIRED TO HAVE P-TRAPS.
  
 2. 2020 914.1 CIRCUIT VENT PERMITTED - THE FIXTURE
 DRAINS OF THE FIXTURES BEING CIRCUIT VENTED SHALL
 CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH DRAIN
 BEING CIRCUIT VENTED. CANNOT CONNECT VERTICALLY.
  
 3. 2020 FPC 1002.4.1 TRAP SEAL PROTECTION - TRAPS
 SUBJECT TO EVAPORATION ARE REQUIRED TO HAVE PROTECTION.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293