2022-09-15 13:22:52ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL ELECTRIC SERVICES THAT WILL COMPLY
 WITH NEC 230.72. GROUPING OF DISCONNECTS.
 (A) GENERAL. THE TWO TO SIX DISCONNECTS AS PERMITTED IN
 230.71
 SHALL BE GROUPED. EACH DISCONNECT SHALL BE MARKED TO
 INDICATE
 THE LOAD SERVED.
 2) PLEASE PROVIDE A CORRECTED ELECTRIC FLOOR PLAN AND
 RISER DIAGRAM AS PER THE ABOVE CHANGES. NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  