Plan Review Notes For Permit 22080216 |
Permit Number |
22080216 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-09-15 13:22:52 | ELECTRIC REVIEW FAILED | | 1) PLEASE DETAIL ELECTRIC SERVICES THAT WILL COMPLY | | WITH NEC 230.72. GROUPING OF DISCONNECTS. | | (A) GENERAL. THE TWO TO SIX DISCONNECTS AS PERMITTED IN | | 230.71 | | SHALL BE GROUPED. EACH DISCONNECT SHALL BE MARKED TO | | INDICATE | | THE LOAD SERVED. | | 2) PLEASE PROVIDE A CORRECTED ELECTRIC FLOOR PLAN AND | | RISER DIAGRAM AS PER THE ABOVE CHANGES. NEC 215.5 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | | | |
|