2022-08-31 10:55:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22080216 5812 S DIXIE HWY
  
 1ST REVIEW
 8/31/2022
 PLUMBING COMMENTS: DENIED
  
 PROVISO: MANUFACTURER'S SPECIFICATION/INSTALLATION
 MANUAL FOR THE FOLLOWING SHALL BE ON SITE PRIOR TO
 FINAL INSPECTION:
 WATER HEATER
 BACKFLOW PREVENTER DEVICES
 THERMOSTATIC MIXING VALVES
 PLUMBING FIXTURES
  
 1. PER WPB CCCM C. III. ALL GENERAL SERVICE
 (COMMERCIAL) AND MULTI-FAMILY DWELLINGS WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER.
 SPECIFY AND FURNISH A BACKFLOW PREVENTION ASSEMBLY FOR
 EACH TENANT SPACE POINT OF ENTRY. PROVIDE A DETAIL.
 PLEASE NOTE, A CHECK VALVE IS NOT A COMPLIANT DEVICE.
  
 SEPARATE BACKFLOW PERMITS ARE REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME.
  
 2. P-101: PER WPB FBC 107.2.1, CONFIRM ON THE PLAN THAT
 WATER SERVICE SHALL CONNECT TO EXISTING BACKFLOW
 PREVENTER AT METER; INDICATE TYPE. UP TO DATE
 CERTIFICATION FOR THE DEVICE SHALL BE ON SITE FOR FINAL
 INSPECTION. WPB CCCM C.III, I-2(A)
  
 3. P-102: PER FBC 1210.2.2 AND FBC PL 310.3, WALLS AND
 PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT
 SURFACE TO A HEIGHT NOT LESS THAN 4 FEET ABOVE THE
 FLOOR. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL BE
 "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 4. P-101/WATER HEATER DETAIL & RISER DIAGRAM: PER WPB
 FBC 107.2.1, FBC PL 606.1 AND 503.1, PROVIDE DEDICATED
 SHUT OFF VALVE FOR COLD WATER TO FAUCET AND FOR COLD
 WATER TO WATER HEATER.
  
 5. P-101/WATER HEATER DETAIL: PER WPB FBC 107.2.1 AND
 FBC PL 419.5, PROVIDE AND SPECIFY AN ASSE 1070
 COMPLIANT WATER-TEMPERATURE LIMITING DEVICE. PROVIDE
 DETAIL.
  
 6. P-101: A HOSE BIB IS SHOWN ON FLOOR PLAN BUT NOT ON
 RISER DIAGRAM, PER WPB FBC 107.2.1, CLARIFY AND
 RECONCILE.
  
 7. P-101: PER FBC PL 606.2, PROVIDE A SHUT-OFF VALVE
 FOR THE HOSE BIB.
  
 8. PER FBC PL 608.1, HOSE BIB SHALL BE PROVIDED WITH A
 HOSE CONNECTION VACUUM BREAKER.
  
 9. P-101: PER WPB FBC 107.2.1, PLEASE SPECIFY MATERIAL
 FOR NEW 1 INCH UNDERGROUND WATER SERVICE.
  
 10. P-101: PER WPB FBC 107.2.1, PLEASE SPECIFY MATERIAL
 FOR NEW 1 INCH ABOVE GROUND
 WATER SERVICE GOING INTO BUILDING.
  
 11. P-101/WATER SERVICE RISER GOING INTO BUILDING: THE
 PLANS ARE UNCLEAR AS TO WHETHER THE RISER IS ON THE
 EXTERIOR FACE OF THE WALL, THE INTERIOR FACE OF THE
 WALL OR INSIDE OF THE WALL. PER WPB FBC 107.2.1,
 PROVIDE DETAIL OF RISER; PROVIDE SUPPORTS, SLEEVING,
 APPLICABLE PROTECTION OF PIPING, ETC. MAINTAIN
 INTEGRITY OF THE WALL.
  
 12. P-101: A CHECK VALVE IS SHOWN IN THE CEILING OF
 EACH SPACE ON THE RISER DIAGRAM; A SERVICE SHUT-OFF
 VALVE IS SHOWN IN THE CEILING ON THE FLOOR PLAN. PER
 WPB FBC 107.2.1, PLEASE CLARIFY AND RECONCILE THE
 DRAWINGS. PLEASE NOTE THAT A CHECK VALVE IS NOT A
 COMPLIANT BACKFLOW PREVENTER DEVICE.
  
 13. P-101: PROVIDE SIZE OF SERVICE SHUT-OFF VALVE IN
 THE CEILING. PER FBC PL 603.1 AND 606.1(2), THE MINIMUM
 SIZE SHALL BE 3/4 INCH.
  
 14. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL
 BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND
 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS
 STATING THE SAME.
  
 15. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 16. PER WPB FBC 107.2.1, PROVIDE ENERGY EFFICIENCY FOR
 WATER HEATER; COMPLY WITH FBC EC TABLE C404.2
  
 17. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT."
  
 18. PER WPB FBC 107.2.1, PROVIDE PLUMBING FIXTURE
 SCHEDULE INDICATING FIXTURE TYPE AND DESCRIPTION (I.E.
 WC-WATER CLOSET, ELONGATED FLOOR MOUNTED TANK TYPE 1.28
 GPF, ADA COMPLIANT, OPEN FRONT ELONGATED SEAT). INCLUDE
 DFU AND DRAIN SIZE/WATER SUPPLY FU AND CONNECTION SIZE
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  
  