2022-08-31 10:55:27 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22080216 5812 S DIXIE HWY |
| |
| 1ST REVIEW |
| 8/31/2022 |
| PLUMBING COMMENTS: DENIED |
| |
| PROVISO: MANUFACTURER'S SPECIFICATION/INSTALLATION |
| MANUAL FOR THE FOLLOWING SHALL BE ON SITE PRIOR TO |
| FINAL INSPECTION: |
| WATER HEATER |
| BACKFLOW PREVENTER DEVICES |
| THERMOSTATIC MIXING VALVES |
| PLUMBING FIXTURES |
| |
| 1. PER WPB CCCM C. III. ALL GENERAL SERVICE |
| (COMMERCIAL) AND MULTI-FAMILY DWELLINGS WATER USERS |
| WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW |
| ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF |
| HAZARD POSED BY THE WATER USER. |
| SPECIFY AND FURNISH A BACKFLOW PREVENTION ASSEMBLY FOR |
| EACH TENANT SPACE POINT OF ENTRY. PROVIDE A DETAIL. |
| PLEASE NOTE, A CHECK VALVE IS NOT A COMPLIANT DEVICE. |
| |
| SEPARATE BACKFLOW PERMITS ARE REQUIRED TO BE SUBMITTED |
| PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS |
| APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| EMAILING A COMPLETED PERMIT APPLICATION TO |
| [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| AND UPLOAD PLANS AT THE SAME TIME. |
| |
| 2. P-101: PER WPB FBC 107.2.1, CONFIRM ON THE PLAN THAT |
| WATER SERVICE SHALL CONNECT TO EXISTING BACKFLOW |
| PREVENTER AT METER; INDICATE TYPE. UP TO DATE |
| CERTIFICATION FOR THE DEVICE SHALL BE ON SITE FOR FINAL |
| INSPECTION. WPB CCCM C.III, I-2(A) |
| |
| 3. P-102: PER FBC 1210.2.2 AND FBC PL 310.3, WALLS AND |
| PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, URINALS AND |
| WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NON-ABSORBENT |
| SURFACE TO A HEIGHT NOT LESS THAN 4 FEET ABOVE THE |
| FLOOR. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL BE |
| "HARD." THE INTENT OF THIS SECTION IS THAT THE |
| SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS |
| EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME |
| ABSORBENT AND THUS, NOT READILY CLEANABLE AND |
| SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH |
| HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF |
| SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS |
| APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED |
| PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED |
| PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL. |
| |
| 4. P-101/WATER HEATER DETAIL & RISER DIAGRAM: PER WPB |
| FBC 107.2.1, FBC PL 606.1 AND 503.1, PROVIDE DEDICATED |
| SHUT OFF VALVE FOR COLD WATER TO FAUCET AND FOR COLD |
| WATER TO WATER HEATER. |
| |
| 5. P-101/WATER HEATER DETAIL: PER WPB FBC 107.2.1 AND |
| FBC PL 419.5, PROVIDE AND SPECIFY AN ASSE 1070 |
| COMPLIANT WATER-TEMPERATURE LIMITING DEVICE. PROVIDE |
| DETAIL. |
| |
| 6. P-101: A HOSE BIB IS SHOWN ON FLOOR PLAN BUT NOT ON |
| RISER DIAGRAM, PER WPB FBC 107.2.1, CLARIFY AND |
| RECONCILE. |
| |
| 7. P-101: PER FBC PL 606.2, PROVIDE A SHUT-OFF VALVE |
| FOR THE HOSE BIB. |
| |
| 8. PER FBC PL 608.1, HOSE BIB SHALL BE PROVIDED WITH A |
| HOSE CONNECTION VACUUM BREAKER. |
| |
| 9. P-101: PER WPB FBC 107.2.1, PLEASE SPECIFY MATERIAL |
| FOR NEW 1 INCH UNDERGROUND WATER SERVICE. |
| |
| 10. P-101: PER WPB FBC 107.2.1, PLEASE SPECIFY MATERIAL |
| FOR NEW 1 INCH ABOVE GROUND |
| WATER SERVICE GOING INTO BUILDING. |
| |
| 11. P-101/WATER SERVICE RISER GOING INTO BUILDING: THE |
| PLANS ARE UNCLEAR AS TO WHETHER THE RISER IS ON THE |
| EXTERIOR FACE OF THE WALL, THE INTERIOR FACE OF THE |
| WALL OR INSIDE OF THE WALL. PER WPB FBC 107.2.1, |
| PROVIDE DETAIL OF RISER; PROVIDE SUPPORTS, SLEEVING, |
| APPLICABLE PROTECTION OF PIPING, ETC. MAINTAIN |
| INTEGRITY OF THE WALL. |
| |
| 12. P-101: A CHECK VALVE IS SHOWN IN THE CEILING OF |
| EACH SPACE ON THE RISER DIAGRAM; A SERVICE SHUT-OFF |
| VALVE IS SHOWN IN THE CEILING ON THE FLOOR PLAN. PER |
| WPB FBC 107.2.1, PLEASE CLARIFY AND RECONCILE THE |
| DRAWINGS. PLEASE NOTE THAT A CHECK VALVE IS NOT A |
| COMPLIANT BACKFLOW PREVENTER DEVICE. |
| |
| 13. P-101: PROVIDE SIZE OF SERVICE SHUT-OFF VALVE IN |
| THE CEILING. PER FBC PL 603.1 AND 606.1(2), THE MINIMUM |
| SIZE SHALL BE 3/4 INCH. |
| |
| 14. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL |
| BE LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND |
| 605.2.1. PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS |
| STATING THE SAME. |
| |
| 15. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| |
| 16. PER WPB FBC 107.2.1, PROVIDE ENERGY EFFICIENCY FOR |
| WATER HEATER; COMPLY WITH FBC EC TABLE C404.2 |
| |
| 17. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL |
| 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING |
| LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF |
| 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE |
| A MINIMUM SLOPE OF 1/8 INCH PER FOOT." |
| |
| 18. PER WPB FBC 107.2.1, PROVIDE PLUMBING FIXTURE |
| SCHEDULE INDICATING FIXTURE TYPE AND DESCRIPTION (I.E. |
| WC-WATER CLOSET, ELONGATED FLOOR MOUNTED TANK TYPE 1.28 |
| GPF, ADA COMPLIANT, OPEN FRONT ELONGATED SEAT). INCLUDE |
| DFU AND DRAIN SIZE/WATER SUPPLY FU AND CONNECTION SIZE |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER PX928 |
| PLUMBING INSPECTOR BN2148 |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| MOBILE 561-246-0882 |
| |
| |