Plan Review Notes For Permit 22080193 |
Permit Number |
22080193 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-08-22 11:12:43 | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2ND FLOOR BATHS 2 & 3 - SANITARY RISER DIAGRAM - | | 2020 FRC P3108.2.1 - THE WATER CLOSET AND THE SHOWER | | ARE CONNECTED BEFORE THE VENTED FIXTURE CONNECTION. | | ONLY ONE BATHROOM GROUP FIXTURE IS ALLOWED UPSTREAM OF | | THE VENTED FIXTURE CONNECTION. | | | | 2. 2ND FLOOR BATH 4 SANITARY RISER DIAGRAM - 2020 FRC | | P3108.2.1 - THE WATER CLOSET AND THE SHOWER ARE | | CONNECTED BEFORE THE VENTED FIXTURE CONNECTION. ONLY | | ONE BATHROOM GROUP FIXTURE IS ALLOWED UPSTREAM OF THE | | VENTED FIXTURE CONNECTION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] |
|