Plan Review Notes
Plan Review Notes For Permit 22080171
Permit Number 22080171
Review Stop G
Sequence Number 1
Notes
Date Text
2022-10-12 13:01:461ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FGC 402.3 - USING THE LONGEST RUN METHOD, AT
 175 FEET FOR PE ON 2 PSI INLET WITH 1 PSI DROP, YOU
 ONLY HAVE 1,170K BTU AVAILABLE ON 1" PE, AND NEED
 1,194K BTU. PLEASE CHECK THE SIZING AND RECONFIGURE.
 YOU'VE ALSO DETAILED THE PRESSURE AT THE SPLIT TO THE
 RANGE AS 8" W.C., WHICH IS LESS THAN THE 1 PSI ON THE
 ORIGINAL SIZE CHART SHOWN TO SUPPLY ALL THE WAY TO THE
 GENERATOR. WHEN USING THE LONGEST RUN METHOD, YOU CAN
 USE ONLY ONE SIZE CHART PER PRESSURE ZONE.
  
 2. 2020 FRC G2415.14 - SHOW BETTER DETAILS FOR SLEEVING
 TO SHOW COMPLIANCE WITH THIS SECTION. YOUR DRAWING
 INDICATE THE SLEEVES TERMINATE BELOW GRADE. THE SLEEVES
 THAT TERMINATE INDOORS MUST TERMINATE IN "AN OCCUPIABLE
 PORTION OF THE BUILDING". IF THE RANGE IS FIXED IN
 PLACE, IT CANNOT TERMINATE BEHIND IT. THE SLEEVE CANNOT
 TERMINATE BEHIND THE FIREPLACE.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]