2022-10-12 13:01:46 | 1ST GAS REVIEW |
| |
| V7 FPC - 2020 FLORIDA PLUMBING CODE |
| V7 FGC - 2020 FLORIDA FUEL GAS |
| V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| 2021 F.S. - 2021 FLORIDA STATUTES |
| 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| FBC CHAPTER 1 |
| |
| THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| |
| 1. 2020 FGC 402.3 - USING THE LONGEST RUN METHOD, AT |
| 175 FEET FOR PE ON 2 PSI INLET WITH 1 PSI DROP, YOU |
| ONLY HAVE 1,170K BTU AVAILABLE ON 1" PE, AND NEED |
| 1,194K BTU. PLEASE CHECK THE SIZING AND RECONFIGURE. |
| YOU'VE ALSO DETAILED THE PRESSURE AT THE SPLIT TO THE |
| RANGE AS 8" W.C., WHICH IS LESS THAN THE 1 PSI ON THE |
| ORIGINAL SIZE CHART SHOWN TO SUPPLY ALL THE WAY TO THE |
| GENERATOR. WHEN USING THE LONGEST RUN METHOD, YOU CAN |
| USE ONLY ONE SIZE CHART PER PRESSURE ZONE. |
| |
| 2. 2020 FRC G2415.14 - SHOW BETTER DETAILS FOR SLEEVING |
| TO SHOW COMPLIANCE WITH THIS SECTION. YOUR DRAWING |
| INDICATE THE SLEEVES TERMINATE BELOW GRADE. THE SLEEVES |
| THAT TERMINATE INDOORS MUST TERMINATE IN "AN OCCUPIABLE |
| PORTION OF THE BUILDING". IF THE RANGE IS FIXED IN |
| PLACE, IT CANNOT TERMINATE BEHIND IT. THE SLEEVE CANNOT |
| TERMINATE BEHIND THE FIREPLACE. |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| |
| RYAN W. BROWN |
| CHIEF PLUMBING INSPECTOR |
| OFFICE: 561-805-6692 |
| CELL: 561-517-4293 |
| EMAIL: [email protected] |