2022-09-14 12:49:37 | 1ST REVIEW FBC-2020 RES. GAS |
| PERMIT- 22080127 |
| 9/14/22 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) P3: PROVIDE A GAS RISER DRAWING- SEC. 107.3.5.3 WPB. |
| PLEASE INCLUDE THE FOLLOWING INFORMATION ON THE DRAWING |
| PER CHAPTER 24 FBC RES. |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) P3: PROVIDE A GAS WATER HEATER SCHEDULE ON THE PLAN |
| LISTING MAKE AND MODEL, BTU CAPACITY, AND EFFICIENCY |
| RATING- SEC. G2439.1 FBC RES. PLEASE INCLUDE THE |
| EFFICIENCY COMPLIANCE DATA IN THE ENERGY FORM R405- |
| 2020. |
| |
| 3) P3: IT APPEARS THE WATER HEATER IS WITHIN 4 FT. OF |
| THE BATHROOM WINDOW. PLEASE VERIFY THE WINDOW IS |
| NON-OPERABLE OR RELOCATE THE UNIT- SEC. G2427.8 FBC |
| RES. |
| |
| 4) P3: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO |
| THE RANGE AND PROVIDE CALCULATIONS- SEC. G2407.1 FBC |
| RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |