Plan Review Notes For Permit 22080126 |
Permit Number |
22080126 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-08-05 13:47:08 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS AN INDICATION ON THE CONTRACT & FLOOR PLAN | | PROPOSED ENGINEERED WOOD FLOORING, BUT NO SPEC SHEET | | NOR A PRODUCT NAME. | | | | ENGINEERED WOOD FLOORING FLOORING IS MANUFACTURED | | AROUND THE WORLD AND NOT ALL ARE TESTED AND MEETING | | LISTED AND NFPA STANDARDS. | | | | PER NFPA 101, CH 30 | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | ACCORDANCE WITH | | SECTION 10.2. | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | 10.2.2.2 | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | HAVE A | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE LVT | | FLOORING NAME AND THE PRODUCT SPEC SHEETS OF THE | | PROPOSED FINISHED | | ENGINEERED WOOD FLOORING INDICATING THE FIRE BEHAVIOR | | RATING. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|