Plan Review Notes
Plan Review Notes For Permit 22080081
Permit Number 22080081
Review Stop G
Sequence Number 1
Notes
Date Text
2022-08-05 13:30:391ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 22080081
 8/5/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SCOPE OF WORK FOR THE PERMIT APPEARS TO BE A
 NEW, NOT REPLACED 180,000 BTU GAS-FIRED TANKLESS WATER
 HEATER TO BE INSTALLED ON THE EXTERIOR OF THE
 RESIDENCE. BASED ON WPB BUILDING DEPARTMENT RECORD
 PLANS UNDER PERMIT-03061107, THE EXISTING WATER HEATER
 IS A 40,000 BTU STORAGE TYPE WATER HEATER INSTALLED ON
 THE INTERIOR OF THE RESIDENCE. THE RISER DRAWING
 SUBMITTED UNDER PERMIT- 22080050 FOR A GAS-FIRED
 GENERATOR SHOWS A 76,000 BTU HEATER INSIDE THE HOUSE.
 REFER TO SECS. G2412.3 & G2412.4 FBC RES AND PROVIDE A
 COMPLETE GAS RISER FOR THE RESIDENCE THAT INCLUDES THE
 FOLLOWING INFORMATION:
  
 A) DELIVERY PRESSURE AT THE METER.
 B) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 C) TYPES AND SIZES OF PIPING SUPPLYING THE EXISTING
 APPLIANCES AND THE NEW WATER HEATER.
 D) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 E) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 F) LOCATIONS OF REGULATORS & SHUTOFF VALVES.
 G) OUTLET PRESSURES AT REGULATORS.
 H) PIPE SIZING TABLES.
  
 2) PROVIDE A BASIC FLOOR PLAN DRAWING SHOWING THE
 LOCATION OF THE WATER HEATER WITH REQUIRED EXHAUST
 OUTLET CLEARANCES TO AIR INTAKES AND OPERABLE OPENINGS
 INTO THE BUILDING SUCH AS WINDOWS AND DOORS- SEC.
 G2439.1 FBC RES.
 CORRECTED PLANS.
  
 3) SUBMIT A GAS PERMIT APPLICATION- SEC. 105.1 WPB. THE
 PLUMBING PERMIT APPLICATION WILL BE CONVERTED TO A
 SUB-PERMIT WHEN THE PRIMARY GAS PERMIT IS RECEIVED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  