2022-08-05 11:34:471ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 22080050
 8/5/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) GAS RISER: PLEASE SHOW THE TYPE AND SIZE OF STEEL
 PIPING FROM THE METER TO THE 1ST TEE, AND FROM THE TEE
 TO THE PE RISER- SECS. G2412.3, G2412.4, & G2415.11.1
 FBC RES.
  
 2) GAS RISER: PLEASE NOTE PERMIT 22080081 SHOWS A
 180,000 BTU EXTERIOR TANKLESS WATER HEATER WHICH IS NOT
 SHOWN ON THE RISER DRAWING- SEC. 107.2.1 WPB.
  
 3) SURVEY: THE NOTE SPECIFYING THE GENERATOR EXHAUST TO
 BE 5 FT. FROM OPENINGS NEEDS TO BE CORRECTED TO
 INDICATE 10 FT. FROM AIR INTAKES INTO THE BUILDING- SEC
 R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  