2022-08-04 12:58:04REVIEW COMMENTS - FIRE
  
 WHAT ARE THE SIZES OF THE PROPOSED TENTS ?
  
 PER FL STATUTE 633.202: (17) A TENT UP TO 900 SQUARE
 FEET IS EXEMPT FROM THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING THE NATIONAL CODES INCORPORATED BY REFERENCE.
  
 IF TENT(S) EXCEED 900 SQ/FT, PROVIDE PORTABLE FIRE
 EXTINGUISHERS. EXTINGUISHERS SHALL HAVE A MINIMUM
 RATING OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED
 FIRE EXTINGUISHER COMPANY. TRAVEL DISTANCE TO
 EXTINGUISHERS SHALL NOT EXCEED 75 FEET. PROVIDE TYPE K
 EXTINGUISHERS WHEN COOKING WITH GREASE OR WHEN
 PRODUCING SMOKE OR GREASE-LADEN VAPORS.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 PROVIDE NON-COMBUSTIBLE CANOPY MATERIAL.
  
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]