2022-10-31 11:06:55 | 3RD REVIEW FBC-2020 RES. PLUMBING |
| PERMIT- 22071418 |
| 10/31/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED |
| |
| 1) THE PREVIOUS SHEET 2 PLUMBING PLAN HAS BEEN |
| ABANDONED. THE NEW SANITARY ISOMETRICS ON NEW SHEET 3 |
| ARE MISLABELED AS SUPPLY ISOMETRICS AND HAVE THE |
| FOLLOWING DEFICIENCIES- |
| |
| A) THERE IS ONLY ONE EXISTING VENT SHOWN FOR BOTH THE |
| MASTER BATHROOM AND KITCHEN FIXTURES- SEC. P3101.2.1 |
| FBC RES. PROVIDE A HORIZONTAL WET VENT FOR THE BATHROOM |
| FIXTURES IN ACCORDANCE WITH SEC. P3108.1. THE LAVATORY |
| VENT CAN SERVE AS THE VENT FOR ALL THE BATHROOM |
| FIXTURES PROVIDING THAT THE LAVATORY FIXTURE DRAIN |
| CONNECTS AT A POINT UPSTREAM OF THE OTHER FIXTURE DRAIN |
| CONNECTIONS, WITH THE EXCEPTION OF ONE FIXTURE |
| PERMITTED TO BE CONNECTED UPSTREAM OF THE LAV DRAIN |
| CONNECTION- SEC. P3108.2.1. THE CURRENT PLAN SHOWS TWO |
| FIXTURES LABELED AS TOILETS CONNECTING UPSTREAM. ONE OF |
| THE FIXTURES SHOULD BE LABELED SHOWER. |
| |
| B) THE DRAIN FROM THE DISHWASHER TYPICALLY CONNECTS TO |
| THE SINK DRAIN VIA AN AIR GAP AND ONE SINGLE VENT SHALL |
| BE PROVIDED FOR BOTH OF THE FIXTURES. THE SINK FIXTURE |
| DRAIN SHALL CONNECT TO THE EXISTING BUILDING DRAIN |
| DOWNSTREAM OF THE BATHROOM WET VENT- SECS. P2717.1, |
| P2717.2, P3107.1 & P3108.2.1. |
| |
| C) NO VENTING IS SHOWN FOR THE FIXTURES IN THE HALL |
| BATHROOM. REFER TO COMMENT 1A ABOVE FOR CODE SECTIONS |
| TO REVIEW AND REVISE THE RISER ACCORDINGLY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |