2022-08-19 05:33:38SHEET 1 OF 3 INDICATES IN THE GENERAL SCOPE OF WORK
 NOTES THAT THE MECHANICAL SCOPE OF WORK IS TO ADD 5
 ZONE MINI SPLIT SYSTEM AS SHOWN. SHEET M-1 IS A DRAWING
 OF AN AHU WITH DUCTWORK GOING THROUGHOUT THE RESIDENCE
 TO EACH ROOM. WE HAVE NO RECORDS OF A MECHANICAL SYSTEM
 PREVIOUSLY BEING PERMITTED FOR THIS HOME. PROVIDE A
 CORRECTED SCOPE OF WORK FOR THIS MECHANICAL SYSTEM
 INCLUDING THE ENERGY CALCULATIONS, THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS AND AN ACCURATE
 MECHANICAL DRAWING INDICATING WHAT IS BEING INSTALLED
 AT THE RESIDENCE. THE DOCUMENTS SUBMITTED MUST BE
 SIGNED BY THE DESIGNER. FBC 107.3.5
  
  