Plan Review Notes For Permit 22071418 |
Permit Number |
22071418 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-08-29 13:44:10 | ELECTRIC REVIEW FAILED | | 1) PLEASE PROVIDE ELECTRICAL RISER DIAGRAM, ELECTRIC | | SITE PLAN DETAILING ALL ELECTRICAL AND MECHANICHAL | | EQUIPMENT (AIR CONDITIONING EQUIPMENT MAY NOT BE | | REFLECTED AS TO BE DETERMINED) PLEASE REFLECT ALL | | EQUIPMENT IN PANEL SCHEDULES AND LOAD CALCULATIONS | | (RANGE,DRYER,MINI SPLITS AND WATERHEATER LOADS APPEAR | | TO BE INCORRECT AS PER NEC 220) FBC 107.2 NEC 215.5 220 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|