2022-08-09 11:36:43SIGNATURE REVIEW
 PERMIT- 22071402
 8/9/2022
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE FIRE SPRINKLER PLAN FP1 SHOWING NEW HEADS IN
 EXCESS OF 49, SHALL BEAR THE DIGITAL SIGNATURE AND SEAL
 OF THE ENGINEER WHO PREPARED THE DRAWINGS- FL STATUTES
 633.102(E), 471.025 AND SEC. 61G15-23.005 FLORIDA
 ADMINISTRATIVE CODE PLANS AND DETAILS SUBMITTED
 ELECTRONICALLY SHALL BEAR DIGITAL SIGNATURES AND SEALS-
 SEE FBPE GUIDELINES BELOW.
  
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS GUIDELINES FOR
 ELECTRONIC OR DIGITALLY SIGNED AND SEALED PLANS AND
 DOCUMENTS.
 A DIGITAL SIGNATURE MUST BE UNIQUE TO THE PROFESSIONAL
 ENGINEER USING IT, OBTAINED FROM A THIRD-PARTY
 CERTIFICATION AUTHORITY, AND CAPABLE OF VERIFICATION.
 THE CERTIFICATION AUTHORITY WILL VET THE PE AND PROVIDE
 A PASSWORD-PROTECTED DIGITAL SIGNATURE FILE. (FBPE DOES
 NOT APPROVE OR PROVIDE A LIST OF AUTHORITIES.)
 YOU MAY NOT USE THE DIGITAL OPTION PROVIDED IN ADOBE
 ACROBAT, SINCE IT IS SELF-AUTHENTICATED AND DOES NOT
 USE A THIRD PARTY.
 YOUR DIGITAL SIGNATURE MUST BE LINKED TO THE DOCUMENT
 IN SUCH A WAY THAT ANY CHANGE INVALIDATES THE SIGNATURE
 AND DOCUMENT.
  