Plan Review Notes For Permit 22071316 |
Permit Number |
22071316 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-09-06 10:44:30 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT A COPY OF THE ACTUAL TEST REPORTS FOR THE | | SOUND INSULATION INCLUDING FLAME SPREAD AND SMOKE | | DEVELOPED FOR THE APPLICABLE CONSTRUCTION CONDITIONS. | | THE TEST REPORTS FOR THE PROPOSED UNDERLAYMENT SHALL BE | | BASED ON THE CONCRETE SLAB THICKNESS AND ONY OTHER | | EXISTING SITE CONDITIONS. | | TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM'S: | | E-84, E-90 & E-492. | | - FBC 603.1 FLAME SPREAD - ASTM E 84-09 | | | | - FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04 | | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES | | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM | | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION | | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) | | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM | | E 90. | | | | - FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09 | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA | | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. | | | | | | | | |
|