2023-01-18 13:14:23 | ADDITION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| |
| 1) THE SOIL REPORT NEEDS TO SHOW THE SOIL BEARING |
| CAPACITY - FBC 1803.3 |
| |
| 2) THE BOTTOM STAIR HAND RAIL SHALL CONTINUE TO SLOPE |
| PER - FBC 1014.6 HANDRAIL EXTENSIONS. |
| HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS |
| ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) |
| BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE |
| DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. |
| |
| 3) THE PROVIDED SURVEY SHOWS THE NORTH EXTERIOR WALL AT |
| 7'7" FROM THE PROPERTY LINE - THE NORTH EXTERIOR WALL |
| NEEDS TO BE SHOWN AS 1 HOUR FIRE RATING ( SHOW THE 1 |
| HOUR FIRE RATED WALL ASSEMBLY) PER FBC TABLE 602 - SEE |
| FBC 705.5 FIRE-RESISTANCE RATINGS. EXTERIOR WALLS SHALL |
| BE FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLES 601 |
| AND 602 AND THIS SECTION. THE REQUIRED FIRE-RESISTANCE |
| RATING OF EXTERIOR WALLS WITH A FIRE SEPARATION |
| DISTANCE OF LESS THAN OR EQUAL TO 10 FEET (3048 MM) |
| SHALL BE RATED FOR EXPOSURE TO FIRE FROM BOTH SIDES. |
| |
| 4) THE GROUND FLOOR STILL NEEDS TO SHOW AN ACCESSIBLE |
| ENTRY - FROM THE FIRST REVIEW - 17) PLEASE SHOW THE |
| ACCESSIBLE ROUTE FROM THE ACCESSIBLE PARKING TO THE |
| BUILDING ENTRY - FBC A 202.4 |
| |
| 5) THE SITE PLAN AND THE SOIL REPORT DO NOT SHOW AS |
| DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| DRAWINGS IN PROJECTDOX NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| SPECIFIC TYPE OF E-SIGNATURE). |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |