2023-01-05 08:50:12 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT-22071309 |
| 1/5/2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE |
| 1ST REVIEW IS LISTED BELOW. THE ARCHITECT???S RESPONSE |
| TO THE COMMENT STSTES THAT THE BATHROOM IS FOR PRIVATE |
| USE. PLEASE NOTE THERE ARE NUMBEROUS EXEMPTIONS LISTED |
| UNDER THE FBC ACC SECTIONS CALLED OUT BELOW THAT WILL |
| ALLOW FOR NON-ADA COMPLIANCE FIXTURES TO BE INSTALLED, |
| AND FOR INSTALLATION OF GRAB BAR REINFORCEMENTS ONLY. |
| |
| 4) SHEET 2: REFER TO SEC. 213.1 & 213.2 FBC ACC AND |
| PROVIDE AN ENLARGED DIMENSIONED DRAWING FOR THE NEW |
| TOILET ROOM SHOWING THE FOLLOWING COMPLIANCE DETAILS |
| PER THE FBC ACC: |
| |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| WATER CLOSET- SECTION 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| LAVATORY- SECTION 606.2. |
| C) TURNING SPACE DIAMETER- SECTION 304.3. |
| D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL- |
| SECTION 604.2. |
| E) HEIGHTS OF THE WATER CLOSET SEAT FROM THE FINISHED |
| FLOOR- SECTION 604.4. |
| F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| FROM THE FINISHED FLOOR- SECTION 606.3. |
| G) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOORS TO |
| THE REFLECTIVE SURFACE- SECTION 603.3 |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSET- SECTION 604.5 & 609.4, |
| FIGURES 604. |
| I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROL-- |
| SECTION 604.6. |
| J) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE |
| 604.7. |
| K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| 606.2. |
| |
| ADVISORY: THE DESIGNER OF RECORD SHOULD REVIEW THE |
| FOLLOWING SECTIONS OF THE FBC ACC FOR FURTHER |
| COMPLIANCE INFORMATION AND EXCEPTIONS- SECS. |
| 201.1-201.1.1, 202.3- 202.4.2 & 203.1- 203.15 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |