2022-12-19 16:54:40 | ADDITION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| |
| 1) THE SOIL REPORT NEEDS TO SHOW THE SOIL BEARING |
| CAPACITY - FBC 1803.3 |
| |
| 2) DRAWING 8 OF 8 SHOWS THE STAIR RISERS AT 7.5 INCHES |
| - THE MAXIMUM RISER HEIGHT IS 7 INCHES PER FBC 1011.5.2 |
| RISER HEIGHT AND TREAD DEPTH. |
| STAIR RISER HEIGHTS SHALL BE 7 INCHES (178 MM) MAXIMUM |
| |
| 3) PLEASE PROVIDE GUARD RAIL DETAILS - SHOW THE |
| REQUIRED GUARD RAIL HEIGHT - FBC 1015.3 |
| |
| 4) PLEASE PROVIDE HAND RAIL DETAILS - SHOW THE REQUIRED |
| HAND RAIL HEIGHT - FBC 1014.2 |
| |
| 5) PLEASE SHOW RESTROOM FLOOR AND BASE BOARD FINISHES |
| TO COMPLY WITH FBC 1210.2.1 |
| |
| 6) DRAWING 1 OF 8 SHOWS THE BUILDING CONSTRUCTION TYPE |
| AS IIB CANNOT HAVE COMBUSTIBLE FRAMING - CONSTRUCTION |
| TYPE SHOULD BE VB |
| |
| 7) THE PROVIDED SURVEY SHOWS THE NORTH EXTERIOR WALL AT |
| 7'7" FROM THE PROPERTY LINE - THE NORTH EXTERIOR WALL |
| NEEDS TO BE SHOWN AS 1 HOUR FIRE RATING ( SHOW THE 1 |
| HOUR FIRE RATED WALL ASSEMBLY) PER FBC TABLE 602 - SEE |
| FBC 705.5 FIRE-RESISTANCE RATINGS. EXTERIOR WALLS SHALL |
| BE FIRE-RESISTANCE RATED IN ACCORDANCE WITH TABLES 601 |
| AND 602 AND THIS SECTION. THE REQUIRED FIRE-RESISTANCE |
| RATING OF EXTERIOR WALLS WITH A FIRE SEPARATION |
| DISTANCE OF LESS THAN OR EQUAL TO 10 FEET (3048 MM) |
| SHALL BE RATED FOR EXPOSURE TO FIRE FROM BOTH SIDES. |
| |
| 8) ALL SIGNED AND SEALED DRAWINGS DO NOT SHOW AS |
| DIGITALLY SIGNED IN ADOBE READER - SIGNED AND SEALED |
| DRAWINGS IN PROJECTDOX NEED TO BE |
| DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN |
| ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| SPECIFIC TYPE OF E-SIGNATURE). |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |