Plan Review Notes
Plan Review Notes For Permit 22071309
Permit Number 22071309
Review Stop P
Sequence Number 1
Notes
Date Text
2022-08-25 10:33:201ST REVIEW FBC-2020 PLUMBING
 PERMIT-22071309
 8/25/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 1 INDICATES AN R3 OCCUPANCY BUT THE ENERGY
 CALCULATIONS INDICATE AN OFFICE WHICH IS A B OCCUPANCY
 CLASSIFICATION AND APPEARS TO BE THE CORRECT
 CLASSIFICATION ? SEC. 304.1 FBC B.
  
 2) SHEET 1 & 2: DESIGN CRITERIA- THE PROPOSED PROJECT
 SHALL BE INCOMPLIANCE WITH THE FLORIDA EXISTING
 BUILDING CODE- 7TH EDITION 2020. PLEASE REFER TO SEC.
 301.1 AND INDICATE THE COMPLIANCE PATH METHOD TO BE
 USED.
  
 3) SHEET 1 & 2: REFER TO TABLE 403.1 FBC P AND PROVIDE
 PLUMBING FIXTURE CALCULATIONS INCLUDING A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED NUMBER OF FIXTURES.
 PLEASE NOTE THAT A SERVICE SINK AND DRINKING FOUNTAIN
 MAY BE REQUIRED- SEE FOOTNOTE E AND SEC. 410.2 FOR
 EXCEPTIONS. PLEASE NOTE THE FOLLOWING CONCERNING THE
 FIXTURES:
 A) HOT WATER AT A MINIMUM TEMPERATURE OF 110 DEGREES F
 SHALL BE DELIVERED FROM THE MOP SINK- SEC. 607.1
 B) A MINIMUM OF TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED- ONE HI FOR WHEELCHAIR ACCESS AND ONE LO FOR
 STANDING PERSONS- SEE SEC. 410.3 FBC P, AND 211.2 FBC
 ACC.
  
 4) SHEET 2: REFER TO SEC. 213.1 & 213.2 FBC ACC AND
 PROVIDE AN ENLARGED DIMENSIONED DRAWING FOR THE NEW
 TOILET ROOM SHOWING THE FOLLOWING COMPLIANCE DETAILS
 PER THE FBC ACC:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SECTION 606.2.
 C) TURNING SPACE DIAMETER- SECTION 304.3.
 D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRROR FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACE- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSET- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROL--
 SECTION 604.6.
 J) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONT OF THE WATER CLOSET- SECTION AND FIGURE
 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2.
  
 ADVISORY: THE DESIGNER OF RECORD SHOULD REVIEW THE
 FOLLOWING SECTIONS OF THE FBC ACC FOR FURTHER
 COMPLIANCE INFORMATION AND EXCEPTIONS- SECS.
 201.1-201.1.1, 202.3- 202.4.2 & 203.1- 203.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  