Plan Review Notes For Permit 22071309 |
Permit Number |
22071309 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-08-01 12:14:13 | FIRE REVIEW COMMENTS: | | | | (1) PROVIDE THE OCCUPANT LOAD FOR THE NEW ADDITION. | | NFPA 101, 38.1.7 | | | | (2) PROVIDE THE MEASUREMENT FOR THE COMMON PATH OF | | TRAVEL. NFPA 101, 38.2.5.3.3 | | | | (3) PROVIDE THE TRAVEL DISTANCE MEASUREMENT. NFPA 101, | | 38.2.6 | | | | (4) MARKING OF EGRESS SHALL HAVE SIGNS IN ACCORDANCE | | WITH NFPA 101, SECTION 7.10 & NFPA 101, 38.2.10 | | | | (5) PROVIDE THE INTERIOR FINISH MATERIALS TO COMPLY | | WITH NFPA 101, 38.3.3.2 & NFPA 101, 38.3.3.3 | | | | (6) PROVIDE A PORTABLE FIRE EXTINGUISHER. NFPA 101, | | 38.3.5 | | | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|