2022-10-14 16:12:35PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [ THE PREVIOUS 2 COMMENTS HAVE NOT BEEN RESOLVED.
 THE ANCHOR SIZES AND EMBED DEPTHS FOR THE POOL HEATER
 HAVE NOT BEEN PROVIDED. THE HEATER DOCUMENTS THAT WERE
 SUBMITTED REFER TO A BOLT DOWN KIT, BUT DOES NOT
 SPECIFY THE SIZE, NUMBER, LOCATIONS AND EMBED DEPTHS OF
 THE ANCHORS. ] THE POOL EQUIPMENT IS REQUIRED TO BE
 ANCHORED TO RESIST WINDLOADS AND FLOOD WATER FORCES.
 SPECIFY THE FASTNER TYPE, SIZE, LOCATIONS AND EMBED
 DEPTHS. FBC-R301
  
 2) [ THE PREVIOUS 2 COMMENTS HAVE NOT BEEN RESOLVED.
 THE POOL EQUIPMENT PAD IS SPECIFIED AS 7.0' NAVD. I
 COULD NOT CLEARLY READ THE ELEVATION OF THE RESIDENCE
 BUT IT APPEARED TO BE MORE THAT 7-0' NAVD. THE POOL
 EQUIPMENT IS REQUIRED TO BE AT OR ABOVE THE ELEVATION
 OF THE HABITABLE ARE OF THE RESIDENCE.] THE PROJECT IS
 LOCATED IN A SPECIAL FLOOD HAZARD AREA. THE POOL
 EQUIPMENT IS REQUIRED TO COMPLY WITH FBC-R 322.1.6.
 EQUIPMENT FOR POOLS, SPAS AND WATER FEATURES SHALL BE
 PERMITTED BELOW THE ELEVATION REQUIRED IN SECTION
 R322.2 OR R322.3 PROVIDED IT IS ELEVATED TO THE EXTENT
 PRACTICAL, IS ANCHORED TO PREVENT FLOTATION AND RESIST
 FLOOD FORCES, AND IS SUPPLIED BY BRANCH CIRCUITS THAT
 HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.