Date |
Text |
2022-10-14 16:12:35 | PLAN |
| REVIEW COMMENTS |
| |
| 3RD REVIEW: FBC SEVENTH EDITION (2020) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) [ THE PREVIOUS 2 COMMENTS HAVE NOT BEEN RESOLVED. |
| THE ANCHOR SIZES AND EMBED DEPTHS FOR THE POOL HEATER |
| HAVE NOT BEEN PROVIDED. THE HEATER DOCUMENTS THAT WERE |
| SUBMITTED REFER TO A BOLT DOWN KIT, BUT DOES NOT |
| SPECIFY THE SIZE, NUMBER, LOCATIONS AND EMBED DEPTHS OF |
| THE ANCHORS. ] THE POOL EQUIPMENT IS REQUIRED TO BE |
| ANCHORED TO RESIST WINDLOADS AND FLOOD WATER FORCES. |
| SPECIFY THE FASTNER TYPE, SIZE, LOCATIONS AND EMBED |
| DEPTHS. FBC-R301 |
| |
| 2) [ THE PREVIOUS 2 COMMENTS HAVE NOT BEEN RESOLVED. |
| THE POOL EQUIPMENT PAD IS SPECIFIED AS 7.0' NAVD. I |
| COULD NOT CLEARLY READ THE ELEVATION OF THE RESIDENCE |
| BUT IT APPEARED TO BE MORE THAT 7-0' NAVD. THE POOL |
| EQUIPMENT IS REQUIRED TO BE AT OR ABOVE THE ELEVATION |
| OF THE HABITABLE ARE OF THE RESIDENCE.] THE PROJECT IS |
| LOCATED IN A SPECIAL FLOOD HAZARD AREA. THE POOL |
| EQUIPMENT IS REQUIRED TO COMPLY WITH FBC-R 322.1.6. |
| EQUIPMENT FOR POOLS, SPAS AND WATER FEATURES SHALL BE |
| PERMITTED BELOW THE ELEVATION REQUIRED IN SECTION |
| R322.2 OR R322.3 PROVIDED IT IS ELEVATED TO THE EXTENT |
| PRACTICAL, IS ANCHORED TO PREVENT FLOTATION AND RESIST |
| FLOOD FORCES, AND IS SUPPLIED BY BRANCH CIRCUITS THAT |
| HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| |
| 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH |
| OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |