2022-09-21 14:26:00PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [ THE PREVIOUS COMMENT WAS NOT RESOLVED.] THE POOL
 EQUIPMENT IS REQUIRED TO BE ANCHORED TO RESIST
 WINDLOADS AND FLOOD WATER FORCES. SPECIFY THE FASTNER
 TYPE, SIZE, LOCATIONS AND EMBED DEPTHS. FBC-R301
  
 2) [ THE PREVIOUS COMMENT WAS NOT RESOLVED.]THE PROJECT
 IS LOCATED IN A SPECIAL FLOOD HAZARD AREA. THE POOL
 EQUIPMENT IS REQUIRED TO COMPLY WITH FBC-R 322.1.6.
 EQUIPMENT FOR POOLS, SPAS AND WATER FEATURES SHALL BE
 PERMITTED BELOW THE ELEVATION REQUIRED IN SECTION
 R322.2 OR R322.3 PROVIDED IT IS ELEVATED TO THE EXTENT
 PRACTICAL, IS ANCHORED TO PREVENT FLOTATION AND RESIST
 FLOOD FORCES, AND IS SUPPLIED BY BRANCH CIRCUITS THAT
 HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.