Plan Review Notes For Permit 22071250 |
Permit Number |
22071250 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-09-21 14:26:00 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) [ THE PREVIOUS COMMENT WAS NOT RESOLVED.] THE POOL | | EQUIPMENT IS REQUIRED TO BE ANCHORED TO RESIST | | WINDLOADS AND FLOOD WATER FORCES. SPECIFY THE FASTNER | | TYPE, SIZE, LOCATIONS AND EMBED DEPTHS. FBC-R301 | | | | 2) [ THE PREVIOUS COMMENT WAS NOT RESOLVED.]THE PROJECT | | IS LOCATED IN A SPECIAL FLOOD HAZARD AREA. THE POOL | | EQUIPMENT IS REQUIRED TO COMPLY WITH FBC-R 322.1.6. | | EQUIPMENT FOR POOLS, SPAS AND WATER FEATURES SHALL BE | | PERMITTED BELOW THE ELEVATION REQUIRED IN SECTION | | R322.2 OR R322.3 PROVIDED IT IS ELEVATED TO THE EXTENT | | PRACTICAL, IS ANCHORED TO PREVENT FLOTATION AND RESIST | | FLOOD FORCES, AND IS SUPPLIED BY BRANCH CIRCUITS THAT | | HAVE GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. | | | | 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|