2022-08-01 09:58:07 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| PERMIT- 22071250 |
| 8/1/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 4: THE 15.9 HR. POOL WATER TURNOVER RATE AT |
| LOW SPEED EXCEEDS THE MAXIMUM 12 HR. RATE SPECIFIED IN |
| SEC. 9.1.3 ANSI/APSP/ICC-5 2011. |
| |
| 2) SHEET 4: PROVIDE THE PUMP CURVE ON THE SHEET MARKED |
| UP TO SHOW THE TDH AND FLOW RATES OF THE SYSTEM- SECS. |
| 4.4.9, 4.4.9.1 ANSI/APSP/ICC-7 & R4501.7.2 & R4501.7.3 |
| FBC RES. |
| |
| 3) SHEET 4: CORRECT THE EQUIPMENT ANCHORING NOTE |
| SPECIFYING MFGR?S NOA. THE NOA DOES NOT EXIST. PLEASE |
| PROVIDE ANCHORING METHOD BY MFGR?S SPECIFICATIONS AND |
| SHOW THE TYPE AND SIZE OF ANCHOR BOLT OR TAPCON |
| INCLUDING DEPTH OF EMBEDMENT AND ANCHOR EDGE DISTANCE |
| FROM SLAB END- SEC. R4501.22 FBC RES. |
| |
| 4) SHEET 1: PLEASE NOTE THE POOL AND SPA ARE BEING |
| CONSTRUCTED IN A FLOOD HAZARD AREA. BASED ON THE NOTE |
| FOR THE CONCRETE EQUIPMENT PAD, PLEASE PROVIDE THE SITE |
| PLAN, AND THE EQUIPMENT PAD ELEVATION HEIGHT- SEC. |
| P2601.3 FBC RES. |
| |
| 5) SHEET 4: PLEASE NOTE THAT THE GAS HEATER SHALL BE |
| INSTALLED UNDER A SEPARATE PERMIT- SECS. 105.1, |
| 107.2.1, 107.3.5.3 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |